| 2023-04-28 16:49:18 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE | | | ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY | | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC | | | 61G1 OR FS 471 & FAC 61G15 | | | | | | 2) THE SURVEY DOES NOT SPECIFY OR SHOW THAT THE | | | GENERATOR EXHAUST IS AT LEAST 10 FEET FROM OPENINGS | | | INTO A BUILDING. SUBMIT A SURVEY SHOWING THE LOCATION | | | OF THE GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO | | | BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | | | | | | | |
|