| Plan Review Notes For Permit 22110556 |
| Permit Number |
22110556 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-10 10:02:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE 48 | | | KW GENERATOR THAT WILL BE INSTALLED. FBC 107.2.1 | | | | | | 2) THE GENERATOR PAD ENGINEERING NEEDS TO BE FOR A WIND | | | SPEED OF 170 MPH VULT. FBC AMENDMENTS 120 | | | | | | 3) THE GENERATOR PAD ENGINEEING IS REQUIRED TO HAVE THE | | | ENGINEER'S DIGITAL SIGNATURE ON IT. ELECTRONICALLY | | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. FS 481 & FAC | | | 61G1 OR FS 471 & FAC 61G15 | | | | | | 4) SUBMIT A SURVEY SHOWING THE LOCATION OF THE | | | GENERATOR. THE GENERATOR EXHAUST IS REQUIRED TO BE AT | | | LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | | | | | | | |
|