| Plan Review Notes For Permit 22110523 |
| Permit Number |
22110523 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-18 08:11:45 | 1ST REVIEW FMC | | | PERMIT: 22110523 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS CONVERTED | | | GARAGE. FEC R101.5.1.1 | | | | | | 2) PROVIDE A BATH EXHAUST FAN FOR THE 2ND STORY | | | BATHROOM. FRC R303.3 | | | | | | 3) PROVIDE A RETURN AIR PATH FROM THE 2ND STORY BEDROOM | | | BACK TO THE AHU. FRC M1602.3 | | | | | | 4) GM1 SHEET SHOWS A MINI-SPLIT IN THE HVAC SYMBOLS AND | | | NOTES, WHERE IS THIS MINI-SPLIT TO BE LOCATED? FBC | | | 107.3.5 | | | | | | 5) THE VENTILATION WORDING IN THE GARAGE IS BLURRY, | | | PLEASE PROVIDE A CLEAR DRAWING SO I CAN READ THE | | | INFORMATION. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|