| 2022-12-29 09:54:52 | 1ST REVIEW FMC |
| | PERMIT: 22110511 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND REQUEST: |
| | SHEET M-2: AHU-2 IS LOCATED IN A MECHANICAL ROOM. WHAT |
| | IS TO BE STORED IN THIS MECHANICAL ROOM? RETURN AIR |
| | CANNOT BE TAKEN FROM A MECHANICAL ROOM. FRC M1602.2. |
| | NUMBER 4. |
| | |
| | 2) SHEET M-2: AHU-1 IN THE STORAGE ROOM THAT IS |
| | ACCESSED FROM THE EXTERIOR OF THE HOME IS ALSO IN AN |
| | AREA THAT IS BEING USED AS A PLENUM. PLEASE SHOW WHAT |
| | IS TO BE STORED IN THIS STORAGE ROOM. WITH THE DOUBLE |
| | EXTERIOR DOORS A LAWN MOWER COULD BE STORED THERE, |
| | GASOLINE COULD BE STORED THERE. THIS STORAGE ROOM IS IN |
| | ESSENCE A RETURN AIR PLENUM. FBC 107.3.5 |
| | |
| | 3) SHEET M-2: AHU-3 IS CEILING MOUNTED, HOW IS THIS |
| | SYSTEM ACCESSED FOR SERVICING? THIS UNIT APPEARS TO BE |
| | MOUNTED IN A BATHROOM HALL. PLEASE SHOW HOW THE RETURN |
| | AIR WILL MEET THE REQUIREMENTS OF FRC M1602.2 NUMBER 4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |