2022-12-29 09:54:521ST REVIEW FMC
 PERMIT: 22110511
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST:
  SHEET M-2: AHU-2 IS LOCATED IN A MECHANICAL ROOM. WHAT
 IS TO BE STORED IN THIS MECHANICAL ROOM? RETURN AIR
 CANNOT BE TAKEN FROM A MECHANICAL ROOM. FRC M1602.2.
 NUMBER 4.
  
 2) SHEET M-2: AHU-1 IN THE STORAGE ROOM THAT IS
 ACCESSED FROM THE EXTERIOR OF THE HOME IS ALSO IN AN
 AREA THAT IS BEING USED AS A PLENUM. PLEASE SHOW WHAT
 IS TO BE STORED IN THIS STORAGE ROOM. WITH THE DOUBLE
 EXTERIOR DOORS A LAWN MOWER COULD BE STORED THERE,
 GASOLINE COULD BE STORED THERE. THIS STORAGE ROOM IS IN
 ESSENCE A RETURN AIR PLENUM. FBC 107.3.5
  
 3) SHEET M-2: AHU-3 IS CEILING MOUNTED, HOW IS THIS
 SYSTEM ACCESSED FOR SERVICING? THIS UNIT APPEARS TO BE
 MOUNTED IN A BATHROOM HALL. PLEASE SHOW HOW THE RETURN
 AIR WILL MEET THE REQUIREMENTS OF FRC M1602.2 NUMBER 4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER