Plan Review Notes
Plan Review Notes For Permit 22110511
Permit Number 22110511
Review Stop B
Sequence Number 2
Notes
Date Text
2023-01-07 12:54:142ND BUILDING REVIEW REVISED 1-17-23
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). THE DESIGN FLOOD ELEVATION (DFE)
 SHALL BE AT OR ABOVE 9'0" NAVD.
  
 1.BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17).
 (FLOOD OPENINGS ARE REQUIRED IN THE FOLLOWING ENCLOSED
 SPACES:)
 1A. ROOM 120 GARAGE (FF EL 6.5') 4 VENTS SHOWN
 1B. ROOM 114 STAIRWELL/STORAGE (FF EL 7.75') 1 VENT
 SHOWN
 1C. ROOM 110 MECHANICAL ROOM (FF EL 8.75') NO VENTS
 SHOWN
 1D. ROOM 115 HALL/LOWER LEVEL (FF EL 6.5') 1 VENT SHOWN
 1E. ROOM 118 STORAGE (FF EL 7.75') 2 VENTS SHOWN
  
 2. CORRECTED
  
 3, CORRECTED
  
 4. IDENTIFY THE TYPE (MODEL #) AND LOCATION OF ANY
 FLOOD OPENINGS ON FLOOR PLAN A1.1 FOR ANY ENCLOSED AREA
 BELOW THE DESIGN FLOOD ELEVATION (DFE) OF 9'0" NAVD.
 R322.2.2.1INSTALLATION OF OPENINGS.
 R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 (SEE LIST OF ROOMS ON LINE 1 ABOVE) (IDENTIFY MODEL OF
 SMART VENTS ON FLOOR PLAN A1.1)
  
 5. CORRECTED
  
 6. PROVIDE STRUCTURAL DETAILS OF ELEVATED SLAB.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
 (ARCHITECT STATES E.O.R WILL SUBMIT) (NOT ADDRESSED)
  
 7. CORRECTED
  
 8. CORRECTED
  
 NEW COMMENTS:
  
 9. PER FEMA TECHNICAL BULLITEN #1, SECTION 8.1, THERE
 SHALL BE AT LEAST TWO FLOOD OPENINGS PER ENCLOSED AREA
 BELOW THE DESIGN FLOOD ELEVATION OF 9.00'.
 SECTION 8.1 LOCATION AND MINIMUM NUMBER OF FLOOD
 OPENINGS
 EVERY ENCLOSED AREA IS REQUIRED TO HAVE AT LEAST TWO
 FLOOD OPENINGS ON EXTERIOR WALLS.
 1A. ROOM 120 GARAGE (FF EL 6.5') 4 VENTS SHOWN ON
 ADJACENT WALLS - OK
 1B. ROOM 114 STAIRWELL/STORAGE (FF EL 7.75') 1 VENT
 SHOWN (2ND VENT REQUIRED)
 1C. ROOM 110 MECHANICAL ROOM (FF EL 8.75') NO VENTS
 SHOWN (REVISION TO PLAN PAGE A-1.1 TO SHOW FF EL. AT
 9.00'.) NO FLOOD OPENINGS WILL BE REQUIRED.
 1D. ROOM 115 HALL/LOWER LEVEL (FF EL 6.5') 1 VENT SHOWN
 (2ND VENT REQUIRED)
 1E. ROOM 118 STORAGE (FF EL 7.75') 2 VENTS SHOWN ON
 ADJACENT WALLS - OK
  
 10. SUBMIT A REVISION TO PLAN PAGE A-1.1 WITH THE ABOVE
 CHANGES.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  