| 2022-11-21 14:12:23 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22110511 |
| | 11/21/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P2, P3, & P4: PROVIDE A SANITARY DRAINAGE AND |
| | VENT ISOMETRIC DRAWING- SEC. 107.3.5.3 WPB. |
| | |
| | 2) P2, P3, & P4: THE PLANS SHOW 6 FULL BATHS, 2 HALF |
| | BATHS, 2 LAUNDRY ROOMS AND 2 OTHER SINKS, PLEASE REFER |
| | TO TABLE P3004.1 FBC RES AND PROVIDE DFU CALCULATIONS. |
| | IT APPEARS THE 3-INCH BUILDING DRAIN MAY HAVDE TO BE |
| | INCREASED IN DIAMETER TO 4-INCH- TABLE P3005.4.2. |
| | |
| | 3) P2: SHOW THE LOCATION OF THE REQUIRED CLEANOUT AT |
| | THE JUNCTION OF THE BUILDING DRAIN AND SEWER- SEC. |
| | P3005.2.3. |
| | |
| | 4) A1.3, A1.4 & P-4: PROVIDE COMPREHENSIVE ROOF |
| | DRAINAGE PLANS THAT SHOW THE LOCATIONS OF ALL FLAT ROOF |
| | PRIMARY AND SECONDARY (OVERFLOW) SCUPPERS FOR AREAS |
| | WITH PARAPET WALLS- SECS. R903.4 & R903.4.1 FBC RES. |
| | A) PROVIDE SCUPPER DETAILS SHOWING THE OPENING SIZES |
| | AND ELEVATION HEIGHT ABOVE THE ROOF SURFACE- SEC. |
| | R903.4.1 FBC RES. |
| | |
| | 5) P-4: THE SINK ON THE ROOF TERRACE WHICH IS CONNECTED |
| | TO THE SANITARY SYSTEM SHALL NOT BE OPEN TO RECEIVING |
| | STORMWATER PER SEC. 90-126 (5) WPB CODE OF ORDINANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |