| Plan Review Notes For Permit 22110486 |
| Permit Number |
22110486 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-17 10:05:19 | THERE DOES NOT APPEAR TO BE ANY NEW DOCUMENTS NOR | | | INFORMATION PROVIDED THAT ADDRESS THE PERVIOUS FIRE | | | COMMENTS. | | | | | | THE PREVIOUS FIRE COMMENTS ARE RESUBMITTED BELOW. | | | | | | PLEASE ADDRESS AS APPLICABLE. | | | | | | ******************************************************* | | | ******************************************************* | | | ************************** | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO | | | SPECIFIC LOCATION INDICATED FOR THE PROPOSED DDCV. | | | | | | THE LOCATION IS REQUIRED TO COMPLY WITH NFPA 24. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A HIGHLIGHTED | | | LOCATION FOR THE PROPOSED DDCV. | | | | | | | | | 1A) IS THIS PROPOSED DDCV FOR A FIRE LINE OR DOMESTIC | | | LINE, OR IS IT FOR BOTH? | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR | | | THE PROPOSED DDCV THAT INDICATES COMPLIANCE WITH NFPA. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|