Plan Review Notes
Plan Review Notes For Permit 22110486
Permit Number 22110486
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-12 11:07:211ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110486
 1/12/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION IS FOR A DCDA BACKFLOW PREVENTER
 ASSEMBLY APPARENTLY FOR THE FIRE LINE. PLEASE NOTE
 SUBMITTED PLAN SHEET C6.01 CALLS OUT AN 8-INCH VERTICAL
 ASSEMBLY PLEASE SUBMIT A SPEC SHEET FOR THE DCDA WITH
 APPROVAL STAMP BY THE DESIGN PROFESSIONAL OF RECORD-
 SEC. 107.2.1 WPB.
  
 2) THE SUBMITTED CIVIL PLAN SHEETS IN THE SIGNATURE
 FILE ARE NOT DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER OF RECORD- FL. STATUTE 471.025, AND SECTION
 61G15-23.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  