| Plan Review Notes For Permit 22110486 |
| Permit Number |
22110486 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-12 11:07:21 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22110486 | | | 1/12/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE APPLICATION IS FOR A DCDA BACKFLOW PREVENTER | | | ASSEMBLY APPARENTLY FOR THE FIRE LINE. PLEASE NOTE | | | SUBMITTED PLAN SHEET C6.01 CALLS OUT AN 8-INCH VERTICAL | | | ASSEMBLY PLEASE SUBMIT A SPEC SHEET FOR THE DCDA WITH | | | APPROVAL STAMP BY THE DESIGN PROFESSIONAL OF RECORD- | | | SEC. 107.2.1 WPB. | | | | | | 2) THE SUBMITTED CIVIL PLAN SHEETS IN THE SIGNATURE | | | FILE ARE NOT DIGITALLY SIGNED AND SEALED BY THE | | | ENGINEER OF RECORD- FL. STATUTE 471.025, AND SECTION | | | 61G15-23.005 FAC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|