| Plan Review Notes For Permit 22110471 |
| Permit Number |
22110471 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-06-26 11:00:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, E1 STATES THAT WIND LOAD CALCS AND | | | STRUCTURAL DETAILS ARE TO BE SUBMITTED. NOTE THAT THE | | | DESIGN CRITERIA IS 175MPH PER E1. | | | | | | THE ENGINEERING PREPARED BY ESRA HASANBAS PERSELLIN, PE | | | IS NOT DIGITALLY SIGNED. PLEASE UPLOAD A DIGITALLY OR | | | ELECTRONICALLY SIGNED DOCUMENT. IF MR. PERSELLIN DOES | | | NOT HAVE A DIGITAL OR ELECTRONIC SIGNATURE, A PAPER | | | ORIGINAL MAY BE SUBMITTED TO THE FRONT COUNTER. | | | | | | THE POLE WAS DESIGNED TO 170MPH, SHEET E1 REQUIRES | | | 175MPH. EITHER REVISE E1 TO STATE 170MPH OR REVISE POLE | | | ENGINEERING TO BE 175MPH. | | | | | | | | | |
|