2 |
|
| Notes |
| Date |
Text |
| 2023-01-10 14:20:23 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. | | | NEC 220. | | | NOTE: - DRAWINGS SHOW ON PAGE 2 OF 3 SECTION POOL | | | EQUIPMENT SCHEDULE LISTING AS PART OF THE EQUIPMET A | | | POOL HEATER GULFSTREAM HI150-R-A. | | | BY THE SPECS MINIMUM CIRCUIT AMPACITY 40, MAIN TIME | | | DELAY BREAKER 50 AMPS, AVERAGE RUNNING AMPS 32.8. | | | - DRAWINGS SHOW ON PAGE 3 OF 3 SECTION ELECTRIC RISER A | | | PROPOSED POOL PANEL WITH A 2P30 BREAKER FOR ELECTRIC | | | HEATER. | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|