Plan Review Notes
Plan Review Notes For Permit 22110439
Permit Number 22110439
Review Stop E
Sequence Number 2
Notes
Date Text
2023-01-10 14:20:23FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE.
 NEC 220.
 NOTE: - DRAWINGS SHOW ON PAGE 2 OF 3 SECTION POOL
 EQUIPMENT SCHEDULE LISTING AS PART OF THE EQUIPMET A
 POOL HEATER GULFSTREAM HI150-R-A.
 BY THE SPECS MINIMUM CIRCUIT AMPACITY 40, MAIN TIME
 DELAY BREAKER 50 AMPS, AVERAGE RUNNING AMPS 32.8.
 - DRAWINGS SHOW ON PAGE 3 OF 3 SECTION ELECTRIC RISER A
 PROPOSED POOL PANEL WITH A 2P30 BREAKER FOR ELECTRIC
 HEATER.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  