| 2022-12-02 10:50:06 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22110439 |
| | 12/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2: REFER TO SEC. R4501.6 FBC RES AND PROVIDE |
| | NOTES ON THE PLAN INDICATING THE POOL DESIGN, |
| | CONSTRUCTION AND WORKMANSHIP SHALL BE IN CONFORMITY |
| | WITH THE REQUIREMENTS OF ANSI/APSP/ICC3; ANSI/APSP/ICC |
| | 4; ANSI/ APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC |
| | 7. |
| | |
| | 2) SHEET 2: PROVIDE AN EQUIPMENT SCHEDULE LISTING THE |
| | MAKES AND MODELS OF THE PUMP, FILTER, CHLORINATOR, POOL |
| | HEATER, AND THE MAIN DRAIN ASSEMBLIES- SEC. R4501.6.2 |
| | FBC RES. THE PLAN DOES NOT INDICATE ELECTRIC HEAT PUMP |
| | OR GAS-FIRED POOL HEATER. PLEASE NOTE GAS POOL HEATERS |
| | SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. 105.1 |
| | & 107.2.1 WPB. |
| | |
| | 3) SHEET 2: THE 285 SQUARE FOOTAGE CALCULATION FOR THE |
| | MAIN POOL APPEARS INCORRECT BASED ON THE DIMENSIONS |
| | SHOWN ON THE PLAN, AND ALSO DOES NOT ACCOUNT FOR THE |
| | SQUARE FOOTAGE OF THE SPA THAT IS DRAINING IN TO THE |
| | POOL- SEC. R4501.6.1 & R4501.7.2 FBC RES. |
| | |
| | 4) SHEET 2: THE 4-INCH SUCTION LINES FROM THE SPA TO |
| | THE POOL INCLUDING THE FLOW VELOCITIES OF THE PIPES ARE |
| | NOT ACCOUNTED FOR IN THE TDH CALCULATIONS- SEC. 4.4.9 |
| | ANSI/APSP/ICC-7. |
| | |
| | A) WHAT TYPE OF TERMINATION FITTING WILL BE USED FOR |
| | THE 4-INCH LINES AT THE POOL WALL- R4501.21.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |