Plan Review Notes
Plan Review Notes For Permit 22110439
Permit Number 22110439
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-02 10:50:061ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22110439
 12/2/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: REFER TO SEC. R4501.6 FBC RES AND PROVIDE
 NOTES ON THE PLAN INDICATING THE POOL DESIGN,
 CONSTRUCTION AND WORKMANSHIP SHALL BE IN CONFORMITY
 WITH THE REQUIREMENTS OF ANSI/APSP/ICC3; ANSI/APSP/ICC
 4; ANSI/ APSP/ICC 5; ANSI/APSP/ICC 6; AND ANSI/APSP/ICC
 7.
  
 2) SHEET 2: PROVIDE AN EQUIPMENT SCHEDULE LISTING THE
 MAKES AND MODELS OF THE PUMP, FILTER, CHLORINATOR, POOL
 HEATER, AND THE MAIN DRAIN ASSEMBLIES- SEC. R4501.6.2
 FBC RES. THE PLAN DOES NOT INDICATE ELECTRIC HEAT PUMP
 OR GAS-FIRED POOL HEATER. PLEASE NOTE GAS POOL HEATERS
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- SEC. 105.1
 & 107.2.1 WPB.
  
 3) SHEET 2: THE 285 SQUARE FOOTAGE CALCULATION FOR THE
 MAIN POOL APPEARS INCORRECT BASED ON THE DIMENSIONS
 SHOWN ON THE PLAN, AND ALSO DOES NOT ACCOUNT FOR THE
 SQUARE FOOTAGE OF THE SPA THAT IS DRAINING IN TO THE
 POOL- SEC. R4501.6.1 & R4501.7.2 FBC RES.
  
 4) SHEET 2: THE 4-INCH SUCTION LINES FROM THE SPA TO
 THE POOL INCLUDING THE FLOW VELOCITIES OF THE PIPES ARE
 NOT ACCOUNTED FOR IN THE TDH CALCULATIONS- SEC. 4.4.9
 ANSI/APSP/ICC-7.
  
 A) WHAT TYPE OF TERMINATION FITTING WILL BE USED FOR
 THE 4-INCH LINES AT THE POOL WALL- R4501.21.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  