Plan Review Notes
Plan Review Notes For Permit 22110429
Permit Number 22110429
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-01-11 11:49:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS A SITE PLAN PROVIDED. HOWEVER, THIS IS NO
 SPECIFIC LOCATION INDICATED FOR THE PROPOSED FIRE LINE.
  
 FOR THE OFFICIAL RECORD AND CLARIFICATIONS, PLEASE
 PROVIDE A HIGHLIGHTED LOCATION FOR THE PROPOSED FIRE
 LINE.
  
  
 1A) THERE ARE NO INDICATIONS OF COMPLIANCE WITH NFPA
 24.
  
 THE PROPOSED SHALL BE INSTALLED, INSPECTED AND TESTED
 PER NFPA AND MANUFACTURES SPECIFICATIONS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGMENT ON THE PLAN SHEETS.
  
  
 1B) THERE ARE NO MANUFACTURES SPECIFICATION SHEETS FOR
 THE PROPOSED FIRE LINE THAT INDICATES COMPLIANCE WITH
 NFPA.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 1C) ENSURE THE APPLICABLE JOINT RESTRAINTS ARE
 INSTALLED AND TORQUED PER MANUFACTURES SPECS AND JOINTS
 SHALL NOT BE COVERED OVER PRIOR TO FIRE INSPECTION.
  
 A TORQUE WRENCH SHALL BE ON SITE WITH THE INSTALLING
 CONTRACTOR FOR CONFIRMATION AND VERIFICATION AT THE
 TIME OF FIRE INSPECTION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGMENT ON THE PLAN SHEETS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]