Plan Review Notes
Plan Review Notes For Permit 22110427
Permit Number 22110427
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-16 13:48:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22110427 931 VILLAGE BLVD # 904
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1. A003-A2/TYPICAL RESTROOM PLAN: SPACE BETWEEN SIDE
 WALL AND REAR GRAB BAR AT WATER CLOSET SHALL BE 6
 INCHES, NOT 8 INCHES. FBC ACC 604.5.2
  
 2. A003-A2/ACCESSIBILITY NOTE 7: PER FBC ACC 606.5,
 AMEND NOTE TO READ "WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT PER FBC
 ACCESSIBILITY CODE 606.5".
  
 3. A003-A2: FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 4. A003-A2: PLEASE INDICATE THE DIMENSION IS TO THE
 BOTTOM EDGE OF THE "REFLECTING" SURFACE OF THE BATHROOM
 MIRROR. FBC ACC 603.3
  
 5. DRINKING FOUNTAIN: PLEASE PROVIDE ELEVATION DETAIL
 OF DRINKING FOUNTAIN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 ***A) FBC ACC 306 KNEE AND TOE CLEARANCE
 ***B) FBC ACC 602.4 SPOUT HEIGHT
 ***C) FBC ACC 602.5 SPOUT LOCATION
 ***D) FBC ACC 602.7 SPOUT HEIGHT FOR STANDING PERSONS
  
 6. DRINKING FOUNTAIN: OBJECTS WITH LEADING EDGES MORE
 THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE
 FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH. FBC ACC 307.2
 PROTRUSION LIMITS. PLEASE NOTE, THIS CAN BE CORRECTED
 BY SPECIFYING A CANE APRON FOR THE HIGHER DRINKING
 FOUNTAIN ON THE PLUMBING FIXTURE SCHEDULE
  
 7. A002-A1: PROVIDE CLEAR FLOOR SPACE FOR BREAK ROOM
 SINK. FBC ACC 606.2, 305.3, 305.5
  
 8. PER FBC 1210.2.2, FBC PL 310.3, PROVIDE A SMOOTH,
 HARD, NON-ABSORBENT WALL SURFACE TO A HEIGHT NOT LESS
 THAN 4 FEET ABOVE THE FLOOR WITHIN 2 FEET OF SERVICE
 SINK. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS (INCLUDING EPOXY PAINT), DOES NOT
 MEET THE INTENT OF SECTION 1210.2.2. THE TYPICAL
 MATERIALS USED FOR THIS APPLICATION ARE CERAMIC TILE,
 FIBERGLASS REINFORCED PLASTIC (FRP) PANELS, PHENOLIC
 PANELS, LAMINATED PLASTIC PANELS, PAINTED STEEL AND
 STAINLESS STEEL
  
 9. P001-P1/SANITARY RISER: MAXILINE SERIES 725 SERIES
 WATER TEMP LIMITING DEVICE. IS THIS A SYMMONS
 (7-225-CK-F) MAXLINE THERMOSTATIC WATER TEMPERATURE
 LIMITING DEVICE AND ASSE 1017/1070 COMPLIANT?
 PER WPB FBC 107.2.1, PLEASE CLARIFY ON THE PLANS.
 PROVIDE DETAIL.
  
 10. WATER HEATER DETAIL:
 ***A) SPECIFY AND PROVIDE THERMAL EXPANSION CONTROL
 DEVICE IN THE COLD WATER SUPPLY BETWEEN ANY CHECK
 VALVES, BACKFLOW PREVENTERS AND PRESSURE REDUCING
 VALVES. FBC PL 607.3
 ***B) NOTE SIZES CORRECT TERMINATIONS OF T&P RELIEF
 DISCHARGE PIPE AND AUXILLARY PAN DRAIN. FBC PL 504.6,
 504.7.1, 504.7.2
  
 11. WATER HEATER IS EXISTING AND RELOCATED. PER PER WPB
 FBC 107.3.5.1.3 (5) PLEASE PROVIDE STORAGE CAPACITY AND
 ENERGY EFFICIENCY SHOWING COMPLIANCE WITH FBC EC TABLE
 C404.2.
  
 12. INSULATION SPECIFICATION FOR HOT WATER INSULATION
 COMPLY WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 INSULATION THICKNESS FOR PIPES SMALLER THAN 1 INCH
 DIAMETER SHALL BE 1 INCH.
  
 13. MAXIMUM ALLOWABLE LENGTH OF 3/4 INCH HOT WATER TO
 PUBLIC LAVATORY FAUCET FROM HOT WATER SOURCE IS 1/2
 FOOT. FBC EC C404.5.1, TABLE C404.5.1.
 REGARDING MAXIMUM LENGTHS AND VOLUME OF HOT WATER FROM
 SOURCE TO OUTLET IN GENERAL, PLEASE REFER TO TABLE
 C404.5.1.
 ***A) FOR A PUBLIC LAVATORY FAUCET, USE THE ???PUBLIC
 LAVATORY FAUCETS??? COLUMN IN TABLE C404.5.1.
 ***B) FOR ALL OTHER PLUMBING FIXTURES AND PLUMBING
 APPLIANCES, USE THE ???OTHER FIXTURES AND APPLIANCES???
 COLUMN IN TABLE C404.5.1.
  
 14. PER WPB FBC 107.3.5.1.3 (2) (3) (4), PROVIDE A
 FIXTURE PLUMBING CONNECTION SCHEDULE OF ALL FIXTURES,
 NEW AND RELOCATED INDICATING FIXTURE DRAIN CONNECTION
 SIZE, DFU, WATER CONNECTION SIZE(S) HOT & COLD, WATER
 FLOW RATE/FLUSHING CYCLE. FBC PL TABLE 604.4, TABLE
 709.1
  
 15. PROVIDE MATERIAL SPECIFICATION, SIZE, ROUTING AND
 TERMINATION OF A/C CONDENSATE DRAIN FOR AIR HANDLER
 UNIT AS WELL AS INSULATION SPECIFICATION. FBC PL 314.2,
 314.2.1, 314.2.2, TABLE 314.2.2, FBC EC TABLE 403.2.10
 ***A) PLEASE NOTE, PER WPB CODE OF ORDINANCE CHAPTER
 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE
 (INTERPRET THIS AS ANY CONDENSATION FROM EVAPORATOR
 COILS) SHALL NOT DISCHARGE TO THE CITY UTILITIES
 SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM
 THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. RICK
 ROSSANO IN ENGINEERING AT 561-494-1098 FOR ADDITIONAL
 INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE
 TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, PROVIDE
 ROUTING AND DRYWELL DETAIL.
  
 16. P001-P1/PLUMBING FIXTURE SCHEDULE-MOP SINK: FAUCET
 WITH HOSE END SHALL BE PROVIDED WITH A VACUUM BREAKER.
 FBC PL 608.1
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ALL PLANS TO BE SIGNED AND SEALED BY
 THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  