| Notes |
| Date |
Text |
| 2023-01-23 15:05:30 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | DESIGNER - FBC WPB 107.1 | | | | | | 2) SIGNED AND SEALED DRAWINGS NEED TO SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | |
|