Date Text
2022-12-13 10:08:39 
 ** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY SCAN IS NOT GOOD AND IT???S DIFFICULT TO
 READ. PLEASE PROVIDE A BETTER SCAN OF THE SURVEY. ALSO
 NOTE THAT THE SURVEY MUST BE DATED LESS THAN A YEAR OLD
 AND MUST BE SIGHED BY A FL REGISTERED LAND SURVEYOR.
 THE SURVEY MUST SHOW ANY UTILITY EASEMENTS THAT ARE
 EXISTING ON THE PROPERTY (IF APPLICABLE).
  
 2.) IN A SITE PLAN, PLEASE SHOW THE SETBACK DISTANCE OF
 THE PROPOSED LOCATION OF THE GENERATOR FROM THE
 PROPERTY LINE(S).
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  