2022-11-17 12:29:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NOINDICATION OF COMPLIANCE WITH ANY NFPA
 CODE FOR EMERGENCY POWER STANDBY SYSTEMS
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
  
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF
 THE NORMAL POWER SUPPLY
 AS SPECIFIED IN TABLE 4.1(B)
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT OF
 COMPLIANCE AND THE CLASS, TYPE AND LEVEL.
  
  
  
 2) THERE ARE INDICATIONS OF NAATURAL GAS HOOK UP;
 HOWEVER, THERE IS NO INDICATION OF PIPING LOCATION,
 SIZE. TYPE, ETC. NOR COMPLIANCE WITH NFPA CODES.
  
  
 PER NFPA 54
  
 CHAPTER 1 ADMINISTRATION
 1.1 SCOPE.
 1.1.1 APPLICABILITY.
 1.1.1.1 THIS CODE IS A SAFETY CODE THAT SHALL APPLY TO
 THE INSTALLATION OF FUEL GAS PIPING SYSTEMS,
 APPLIANCES, EQUIPMENT, AND
 RELATED ACCESSORIES AS SHOWN IN 1.1.1.1(A) THROUGH
 1.1.1.1(D).
  
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT OF
 COMPLIANCE AND PLAN SHEETS WITH DETAILS.
  
 IF UNDER SEPARATE PERMIT, PLEASE PROVIDE A NOTE OR THE
 PERMIT #.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL