| 2022-11-17 12:29:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NOINDICATION OF COMPLIANCE WITH ANY NFPA |
| | CODE FOR EMERGENCY POWER STANDBY SYSTEMS |
| | |
| | PER NFPA 110 |
| | |
| | CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY |
| | SYSTEMS (EPSSS) |
| | |
| | 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF |
| | ELECTRICAL |
| | POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO |
| | LOADS FOR |
| | A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND |
| | WITHIN A SPECI FIED TIME FOLLOWING LOSS OR FAILURE OF |
| | THE NORMAL POWER SUPPLY |
| | AS SPECIFIED IN TABLE 4.1(B) |
| | |
| | 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN |
| | HOURS, FOR |
| | WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD |
| | WITHOUT |
| | BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).] |
| | 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN |
| | SECONDS, |
| | THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE |
| | TRANSFER |
| | SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE |
| | 4.1(B) |
| | PROVIDES THE TYPES DEFINED BY THIS STANDARD. |
| | 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF |
| | EQUIPMENT |
| | INSTALLATION, PERFORMANCE, AND MAINTENANCE. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT OF |
| | COMPLIANCE AND THE CLASS, TYPE AND LEVEL. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF NAATURAL GAS HOOK UP; |
| | HOWEVER, THERE IS NO INDICATION OF PIPING LOCATION, |
| | SIZE. TYPE, ETC. NOR COMPLIANCE WITH NFPA CODES. |
| | |
| | |
| | PER NFPA 54 |
| | |
| | CHAPTER 1 ADMINISTRATION |
| | 1.1 SCOPE. |
| | 1.1.1 APPLICABILITY. |
| | 1.1.1.1 THIS CODE IS A SAFETY CODE THAT SHALL APPLY TO |
| | THE INSTALLATION OF FUEL GAS PIPING SYSTEMS, |
| | APPLIANCES, EQUIPMENT, AND |
| | RELATED ACCESSORIES AS SHOWN IN 1.1.1.1(A) THROUGH |
| | 1.1.1.1(D). |
| | |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT OF |
| | COMPLIANCE AND PLAN SHEETS WITH DETAILS. |
| | |
| | IF UNDER SEPARATE PERMIT, PLEASE PROVIDE A NOTE OR THE |
| | PERMIT #. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |