| 2023-02-07 14:30:51 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22110296 |
| | 2/7/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: THE 1/2-INCH GALVANIZED PIPE TO THE |
| | GENERATOR SHALL BE INCREASED IN SIZE TO MINIMUM |
| | 3/4-INCH- TABLE G2413.4(2) FBC RES. |
| | |
| | 2) GAS RISER: SHOW THE TYPE AND SIZE OF PIPE FROM THE |
| | 1-INCH PE TO THE EXISTING TANKLESS WATER HEATER- SEC. |
| | G2413.3 FBC RES. |
| | |
| | 3) GAS RISER: PLEASE SHOW THE EHD OF THE CSST PIPING- |
| | SEC. G2413.3 FBC RES. |
| | |
| | 4) SHEET P1.0: THE MARKED-UP PLAN WILL REQUIRE THE |
| | DIGITAL SIGNATURE AND SEAL OF THE REGISTERED ARCHITECT- |
| | FL STATUTE 481.221 AND SEC. 61G1-16.005 FAC. THE |
| | CONTRACTOR WHO PUT THE MARKINGS ON THE PLAN MAY SUBMIT |
| | HIS OWN FLOOR PLAN SKETCH TO SHOW THE APPLIANCE AND |
| | PIPING LOCATIONS- SEC. 107.2.1 WPB. |
| | |
| | 5) P1.0: THE GENERATOR IS UNDER SEPARATE PERMIT REVIEW |
| | HOWEVER PLEASE NOTE THAT THE GENERATOR EXHAUST SHALL BE |
| | A MINIMUM OF 10 FT. FROM GRAVITY AND MECHANICAL AIR |
| | INTAKES INTO THE BUILDING- R303.5.1 FBC RES. |
| | |
| | 6) P1.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE PER SEC. G2407.1 FBC RES. PLEASE NOTE A TOTAL OF |
| | 3475 CU. FT OF OPEN AIR IS REQUIRED FOR THE 69,500 BTU |
| | RANGE IF USING THE INDOOR VOLUME OF THE SPACE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |