Date Text
2023-01-13 09:40:58JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS
 TO INDICATE REROOFING POP-UP ROOF AREAS 1, 2 & 3; IF
 NOT INDICATE BY PLACING AN X IN THE POP-UP ROOF AREAS;
 IF TO RECEIVE NEW ROOFING PROVIDE A COMPLETE SET OF
 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE
 PROPOSED FLAT ROOF SYSTEM TO BE USED. SUBMITTED
 MIAMI-DADE NOA NO. 18-1023.06 SYSTEM TYPE A (3) CANNOT
 BE USED FOR POP-UP ROOF AREAS 1 & 2 AS PER THE
 SUBMITTED FIELD WITHDRAWAL RESISTANCE TEST REPORT.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  