Plan Review Notes
Plan Review Notes For Permit 22110237
Permit Number 22110237
Review Stop M
Sequence Number 1
Notes
Date Text
2023-04-04 06:39:04THERE IS NOTHING I CAN REVIEW. THERE IS A CLOUDED NOTE
 ADDED TO SHEET M1-01 THAT STATES; GENERATOR WILL BE
 UNDER A SEPARATE MECHANICAL PERMIT APPLICATION AND PLAN
 REVIEW. THIS GENERATOR IS INSIDE A RATED ROOM ON THE
 FIRST FLOOR. THERE IS NO MENTION AS TO THE TYPE OF
 GENERATORGOING INTO THIS GENERATOR ROOM ON THE ORIGINAL
 DRAWINGS, THERE IS NO FUEL LINE DRAWINGS, NO
 VENTILATION DRAWINGS, NO MUFFLER SPECS. NO DESIGN
 SHOWING WHERE THE EXHAUST AND INTAKE ARE TO BE LOCATED
 FOR THIS GENERATOR AND ROOM. I HAVE NOTHING TO REVIEW.
 PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS GENERATOR
 AND GENERATOR ROOM. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  