| Plan Review Notes For Permit 22110237 |
| Permit Number |
22110237 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-04 06:39:04 | THERE IS NOTHING I CAN REVIEW. THERE IS A CLOUDED NOTE | | | ADDED TO SHEET M1-01 THAT STATES; GENERATOR WILL BE | | | UNDER A SEPARATE MECHANICAL PERMIT APPLICATION AND PLAN | | | REVIEW. THIS GENERATOR IS INSIDE A RATED ROOM ON THE | | | FIRST FLOOR. THERE IS NO MENTION AS TO THE TYPE OF | | | GENERATORGOING INTO THIS GENERATOR ROOM ON THE ORIGINAL | | | DRAWINGS, THERE IS NO FUEL LINE DRAWINGS, NO | | | VENTILATION DRAWINGS, NO MUFFLER SPECS. NO DESIGN | | | SHOWING WHERE THE EXHAUST AND INTAKE ARE TO BE LOCATED | | | FOR THIS GENERATOR AND ROOM. I HAVE NOTHING TO REVIEW. | | | PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS GENERATOR | | | AND GENERATOR ROOM. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|