Plan Review Notes For Permit 22110154
Permit Number 22110154
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-15 16:48:56THE DRAWING SUBMITTED FOR THE NEW DUCTWORK DOES NOT
 SHOW THE RETURN AIR PATH FROM THE ROOMS BACK TO THE AHU
 IN THE ATTIC. PROVIDE A DUCT WORK DESIGN THAT SHOWS THE
 RETURN AIR PATH BACK TO THE AHU. FRC M1602.3
  