Plan Review Notes
Plan Review Notes For Permit 22110128
Permit Number 22110128
Review Stop B
Sequence Number 1
Notes
Date Text
2023-07-05 08:52:02WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22110128
 ADD: 4325 GEORGIA AVE.
 CONT: O/B BRADLEY BROOKS
 TEL: 561-635-0601
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 05TH/ 2023
 ACTION: DENIED
  
 1) THE DOLLAR AMOUNT OF $9,000.00 IS EXTREMELY LOW EVEN
 FOR AN O/B (OWNER/BUILDER). 109.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, CANOPIES, ALL LOW VOLTAGE PERMITS, GENERATORS
 & FUEL TANKS WITH FILL STATIONS, GAS PERMIT, POOL,
 JACUZZI AND ASSOCIATED SUB-PERMITS, AWNING, SCREEN
 ENCLOSURES, CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER
 CAST PILE AND OR FOUNDATION OR STRUCTURE ONLY PERMIT
 WILL BE SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH
 PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2) THE SUBMITTED SITE PLAN THE FIGURES ARE TO SMALL TO
 BE DISTINGUISHED WHEN ENLARGED THEY BECOME BLURRED,
 ILLEGIBLE. 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL
 PAPER OR OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL
 MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS
 FOR THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3) THE SUBMITTED DOCUMENT FROM BMB BEST METAL BUILDINGS
 LLC IT APPEARS THE DOCUMENT WAS DOWNLOADED THEN
 UPLOADED AGAIN; THE ELECTRONIC SIGNATURE/ SEAL DOES NOT
 OPEN FOR 3RD PARTY REVIEW.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) PLANS
 IN THE FILE FOLDER, SCANNED, FACSIMILE, DIGITALLY
 CREATED OR COPIED IMAGE OF THE LICENSEE???S SIGNATURE
 SHALL NOT BE USED ON ELECTRONIC/DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 FL. ADMINISTRATIVE CODE 61G15-23.004 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS, REQUIRE 3RD PARTY VERIFICATION.
 1) ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C., MAY BE SIGNED
 DIGITALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE. AS USED HEREIN, THE
 TERMS ???CERTIFICATION AUTHORITY,??? AND ???DIGITAL
 SIGNATURE??? SHALL HAVE THE MEANINGS ASCRIBED TO THEM
 IN SECTIONS 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE
 DOCUMENT IS INVALIDATED IF ANY DATA IN THE DOCUMENT IS
 CHANGED.
  
 4) BMB BEST METAL BUILDINGS LLC SHEET 3 NOTE 4 OR NOTE
 5 INDICATE WIND SPEED ZONES, O/B HAS NOT CIRCLED WHICH
 WIND ZONE THIS BUILDING IS BEING DESIGNED TOO! NOTED
 RISK CATEGORY I. PLEASE NOTE ABLE 1604.5 IN THE 2020
 FBC-BUILDING CODE THIS IS ALLOWED FOR A OPEN STRUCTURE,
 BUT IF THIS STRUCTURE LATER IS ENCLOSED THEN THE RISK
 FACTOR INCREASES FOR THE STRUCTURE II AND WIND SPEED,
 SEE FIGURE 1609.3(3) I BUILDINGS AND FIGURE 1609.3.1 II
 BUILDINGS, 2020 FBC-BUILDING CODE.
  
 5) BMB BEST METAL BUILDINGS LLC SHEETS 4-8A HAVE
 VARIOUS DESIGN FEATURES , BOX FRAME VERSES, BOW FRAME,
 WIDTHS AND HEIGHTS, RAFTER/ COLUMN END FRAME SECTIONS,
 SIDE FRAMING SEE NOTES PAGE 3, AND VARIOUS WALL AND
 BRACING VARYING WITH THE HEIGHT OF THE BUILDING. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 6) SHEET 3 NOTE #9 STATES 29-GAUGE METAL PANELS (ROOF
 PANELS) PLEASE PROVIDE THE PRODUCT APPROVAL FOR ROOF
 PANELS. COMPONENTS & CLADDING. PLEASE SUBMIT THE
 COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 7) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 8) THE SITE PLAN IT APPEARS THE CANOPY IS TO BE PLACED
 AT THE SIDE PROPERTY LINE. HOW ARE YOU GOING TO PROTECT
 THE STRUCTURE FROM FIRE FROM THE NEIGHBORING PROPERTY,
 AND HOW DO YOU INTEND TO COMPLY WITH TABLE 602 OF THE
 2020 FBC-BUILDING CODE FIRE-RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE.
  
 9) VARIOUS SHEETS WITHIN THE ENGINEERING SHEETS SHOW
 WIELDED CONCOCTIONS, ASSUMED AT THE JOBSITE NO NOTES ON
 SHEET 4 STATING FACTORY WELDS. WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 10) NOTE ONLY. SHEET 9 INDICATES THE TOP OF THE FLOOR
 SLAB EVEN WITH GRADE AND MEETING THE MINIMUM CODE
 REQUIREMENT FOR THE DEPTH OF THE FOUNDATION OF ONE
 FOOT. THIS WILL MEET THE MINIMUM CODE REQUIREMENT BUT
 NOT FOR BUILDINGS IF FUTURE WALLS ARE ADDED.
  
 11) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  