| 2023-03-23 09:29:19 | FIRE REVIEW COMMENTS: | | | | | | THE PLAN SUBMISSION DOES NOT HAVE DETAIL TO INDICATE | | | WHAT DOORS WILL HAVE THE CLOSING DEVICES INSTALLED, THE | | | SEQUENCE OF OPERATION ON HOW THE SELF-CLOSING DEVICES | | | WILL BE ACTIVATED, WHAT WILL CAUSE THE CLOSING DEVICE | | | TO OPERATE, AND THE RESPONSE PAGE SUBMITTED TO PREVIOUS | | | COMMENTS IS NOT DESCRIBE ANY THING THAT CAN BE | | | DISCERNED BY THIS REVIEWER. | | | | | | SUBMIT CLEAR AND CONCISE DETAILS OF THE LOCATION, | | | ACTIVATION, OPERATION, ETC. OF THE PROPOSED | | | INSTALLATION. | | | | | | THE INSTALLATION SHALL COMPLY WITH NFPA 80, STANDARD | | | FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, CHAPTER | | | 4.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|