| Plan Review Notes For Permit 22110065 |
| Permit Number |
22110065 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-14 17:53:16 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22110065 | | | 1046 LINCOLN RD | | | | | | 1-EMERGENCY EGRESS | | | SHOW HOW IS EMERGENCY EGRESS PROVIDED WHEN THE OPENINGS | | | HAVE SHUTTERS. SEC. R310.4 FBC-RESIDENTIAL. | | | NOTE: CLARIFY WHAT ARE OPENINGS #5 AND #11. WHY ARE | | | THEY BLANK. | | | | | | 2- REVISE INSTALLATION SCHEDULE. ANCHOR SPACING AT THE | | | BOTTOM OF SHUTTERS IS INCORRECT. NEED TO USE ANCHOR | | | TYPE A1 FOR CONCRETE BLOCK INSTALLATION. SEE SHEET 12 | | | OF 18 OF SHUTTERS PRODUCT APPROVAL. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | NOTE: KEEP IN MIND EDGE DISTANCE EXCLUDES STUCCO | | | FINISH. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|