| 2022-12-29 15:11:30 | 1ST REVIEW FMC | | | PERMIT: 22110052 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHOW ON THE ROOF DRAWING, M2, THAT THE RTU-1, CU-1 | | | AND CU-2 AND COOLER CONDENSER WILL MEET THE GUARD | | | PROTECTION REQUIREMENTS OF FMC 306.5 | | | | | | 2) SHOW ON THE ROOF DRAWING, M2, THAT THE RTU-1, CU-1, | | | CU-2 AND COOLER CONDENSER WILL MEET THE GUARD | | | PROTECTION OF FMC 304.11 | | | | | | 3) ADD A NOTE ON THE DRAWING THAT THE REFRIGERATION | | | WILL REQUIRE A SEPARATE PERMIT AND MECHANICAL REVIEW AS | | | IT WILL NOT BE REVIEWED UNDER THIS PERMIT. | | | | | | 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC C403.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|