Notes
Date Text
2022-12-21 10:45:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS ON THE ELECTICAL PLAN SHEET E
 1 OF EXIT SIGNS LEADING OUT OF THE RESTROOM AND OUT OF
 THE OPENING TO THE REAR EXIT.
  
 HOWEVER, THE RESTROOM DOOR OPENS OUT INTO THE EXIT
 TRAVEL PATH AND RESTRICTS EGRESS DUE TO THE EQUIPMENT
 INSTALLATIONS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
  
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
  
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 7.3.4 MINIMUM WIDTH.
  
 7.3.4.1 THE WIDTH OF ANY MEANS OF EGRESS, UNLESS
 OTHERWISE PROVIDED
 IN 7.3.4.1.1 THROUGH 7.3.4.1.3, SHALL BE AS FOLLOWS:
 (1) NOT LESS THAN THAT REQUIRED FOR A GIVEN EGRESS
 COMPONENT IN THIS
 CHAPTER OR CHAPTERS 11 THROUGH 43
 (2) NOT LESS THAN 36 IN. (915 MM) WHERE ANOTHER PART OF
 THIS CHAPTER
 AND CHAPTERS 11 THROUGH 43 DO NOT SPECIFY A MINIMUM
 WIDTH
  
 7.3.4.1.1* THE WIDTH OF EXIT ACCESS SERVING NOT MORE
 THAN SIX PEOPLE
 AND HAVING A LENGTH NOT EXCEEDING 50 FT (15 M) SHALL
 MEET BOTH OF THE
 FOLLOWING CRITERIA:
 (1) THE WIDTH SHALL BE NOT LESS THAN 18 IN. (455 MM),
 AT AND BELOW A
 HEIGHT OF 38 IN. (965 MM), AND NOT LESS THAN 28 IN.
 (710 MM) ABOVE
 A HEIGHT OF 38 IN. (965 MM).
 (2) A WIDTH OF NOT LESS THAN 36 IN. (915 MM) FOR NEW
 EXIT ACCESS, AND
 NOT LESS THAN 28 IN. (710 MM) FOR EXISTING EXIT ACCESS,
 SHALL BE
 CAPABLE OF BEING PROVIDED WITHOUT MOVING PERMANENT
 WALLS
  
 7.3.4.2 WHERE A SINGLE EXIT ACCESS LEADS TO AN EXIT,
 ITS CAPACITY IN TERMS
 OF WIDTH SHALL BE NOT LESS THAN THE REQUIRED CAPACITY
 OF THE EXIT TO WHICH
 IT LEADS
  
 PLEASE REVIEW AND PROVIDE THE DIMENSION FOR PROPER
 CLEARANCE OR REMOVE THE EXIT SIGN OVER THE OPENING TO
 THE REAR AND PALCE ONE OVER ANY OF THE OTHER EXTERIOR
 DOORS IN THE FRONT.
  
  
 2) THE DOOR SCHEDULE INDICATES LOCKING HARDWARE ON D3
 DOORS.
  
 IF ONE OF THOSE DOORS HAS THE EXIT SIGN MOVED OVER IT,
 THE LOCKING HARDWARE SHALL COMPLY WITH NFPA 101 CH 7,
 MEANS OF EGRESS.
  
 38.2.2.2.3* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED ONLY ON
 PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE DETAILS OR A
 NOTE OF ACKNOWLEDGMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  