| 2022-11-15 13:46:39 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS |
| | SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT |
| | SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER |
| | DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE. |
| | THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE |
| | INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1. |
| | THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC |
| | HANDWASHING PROTECTION FOR TEMPERED WATER. |
| | |
| | 2. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR |
| | THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING |
| | FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD |
| | CONFORM TO ASSE 1070. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - I AM UNABLE TO LOCATE A |
| | DRAIN LOCATION FOR THE WATER HEATER DRAIN PAN AND T&P |
| | RELIEF VALVE FOR THE WATER HEATER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |