| 2022-11-30 09:33:40 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FEX 604.1 - THE CLASSIFICATION OF WORK IS NOT A |
| | LEVEL 1 ALTERATION. RECONFIGURING THE FLOOR SPACE IN AN |
| | AREA OF MORE THAN 50 PERCENT OF THE BUILDING AREA IS A |
| | LEVEL 3 ALTERATION. |
| | |
| | 1. 2020 FBC 454.1.6.1 - COULD YOU PLEASE ADD THE |
| | OCCUPANT LOAD CALCULATION TO VERIFY YOU ARE MEETING THE |
| | REQUIRED FIXTURES. |
| | |
| | 2. 2020 FBC 454.1.6.1.4 - PLEASE SHOW THE REQUIRED HOSE |
| | BIBB (WITH A VACUUM BREAKER) OR SHOW AN ACCESSIBLE ONE |
| | WITHIN 25FT FOR CLEANING OF THE RESTROOMS. |
| | |
| | 3. 2020 FAC 604.8.1.1 - PLEASE SHOW THE SIZE OF THE ADA |
| | WATER CLOSET COMPARTEMENT TO COMPLY WITH A 56"X60" |
| | COMPARTMENT. |
| | |
| | 4. 2020 FPC 905.4 - THE VENTS SHOWN FOR THE WATER |
| | CLOSETS AND THE URINALS ARE NOT COMPLIANT. THE DRY VENT |
| | FOR A FIXTURE NEEDS TO RISE 6" ABOVE THE FLOOD LEVEL |
| | RIM OF THE FIXTURE(S) SERVED BEFORE GOING HORIZONTAL. |
| | |
| | 5. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR |
| | THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING |
| | FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD |
| | CONFORM TO ASSE 1070. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |