| Date |
Text |
| 2022-12-13 07:48:35 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | NOTICE: PLAN SHEETS ARE MIS-LABLED: |
| | |
| | 1. SHEETS 2 THRU 5 ARE FLOOR PLANS NOT SITE PLANS. |
| | 2. SHEETS 6 THRU 19 ARE 3-D ELEVATION RENDERINGS, NOT |
| | FLOOR PLANS. |
| | |
| | PLEASE LABEL YOUR PLAN SHEETS ACCORDING TO STANDARD |
| | NAMING CONVENTIONS: |
| | |
| | 4. PROVIDE A FLOOR PLAN OF THE ENTIRE STRUCTURE. |
| | IDENTIFY THE LOCATION OF WORK. (KITCHEN AND M/BATH) |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 5. PROVIDE SMOKE ALARMS. LOCATE ON FLOOR PLAN. |
| | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| | BUILDING. |
| | |
| | SMOKE ALARMS |
| | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |