| 2022-11-16 15:56:03 | 22101508 440 COLUMBIA DR # 105 |
| | |
| | PLUMBING COMMENTS: REVIEWED FOR COMPLIANCE IN |
| | ACCORDANCE WITH WPB FBC 107.3.5.1.3 |
| | SEE PROVISOS |
| | |
| | PROVISO: PLAN SHEET 3.2/TOILET ELEVATIONS 4, 5, 6 AND |
| | 7: PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE. DETAILS INDICATE |
| | MINIMUM 33 INCHES TO BOTTOM OF GRAB BAR, NOT THE TOP. |
| | PROVIDE REVISED PLAN INDICATING COMPLIANT INSTALLATION. |
| | DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR |
| | TO FIRST INSPECTION. PROCEED AT YOUR OWN RISK. WPB FBC |
| | 107.2.1 AND WPB FBC 107.3.4.1 |
| | |
| | PROVISO: PER FBC 1210.2.2, FBC PL 310.3, WALLS AND |
| | PARTITIONS WITHIN 2 FEET OF SERVICE SINKS SHALL HAVE A |
| | SMOOTH, HARD NON-ABSORBANT SURFACE TO A HEIGHT NOT LESS |
| | THAN 4 FEET ABOVE THE FLOOR. THE FINISH SCHEDULE CALLS |
| | OUT EPOXY PAINT. THIS DOES NOT COMPLY. |
| | SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE |
| | "HARD." THE INTENT OF THIS SECTION IS THAT THE |
| | SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS |
| | EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME |
| | ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| | SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | PROVIDE REVISED PLAN INDICATING COMPLIANT FINISH. |
| | DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR |
| | TO FIRST INSPECTION. PROCEED AT YOUR OWN RISK. WPB FBC |
| | 107.2.1 AND WPB FBC 107.3.4.1 |
| | |
| | PROVISO: PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; |
| | COMPLY WITH FBC EC TABLE C404.2. |
| | PROVIDE MANUFACTURER'S DOCUMENT INDICATING COMPLIANCE. |
| | DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR |
| | TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK. WPB FBC |
| | 107.2.1 AND WPB FBC 107.3.4.1 |
| | |
| | |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO |
| | AVOID VOIDING OF THE PERMIT. |
| | |