| Plan Review Notes For Permit 22101437 |
| Permit Number |
22101437 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-22 16:46:22 | EXTERIOR WALL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | | | | 1) PLEASE PROVIDE AN EXTERIOR WALL DETAIL THAT MATCHES | | | THE EXISTING - 107.2.4 2017 CHAPTER 1 WPB AMENDMENTS | | | FRAMING TYPE (WOOD, METAL)? | | | FRAMING SPACING O.C. | | | SHEATHING Y/N AND IS YES WHAT THICKNESS | | | | | | 2) PLEASE SHOW LATH FASTENERS TO COMPLY WITH R703.7.1 | | | | | | 3) FBC R703.7.2 PLASTER. | | | PLASTERING WITH CEMENT PLASTER SHALL BE NOT LESS THAN | | | THREE COATS WHERE APPLIED OVER ANY TYPE OF | | | CODE-APPROVED LATH AND SHALL BE NOT LESS THAN TWO COATS | | | WHERE DIRECTLY APPLIED OVER MASONRY, CONCRETE, CLAY | | | BRICK, STONE OR TILE. IF THE PLASTER SURFACE IS | | | COMPLETELY COVERED BY VENEER OR OTHER FACING MATERIAL | | | OR IS COMPLETELY CONCEALED, PLASTER APPLICATION NEED BE | | | ONLY TWO COATS, PROVIDED THE TOTAL THICKNESS IS AS SET | | | FORTH IN TABLE R702.1(1). | | | | | | | | | |
|