Plan Review Notes
Plan Review Notes For Permit 22101437
Permit Number 22101437
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-22 16:46:22EXTERIOR WALL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
  
 1) PLEASE PROVIDE AN EXTERIOR WALL DETAIL THAT MATCHES
 THE EXISTING - 107.2.4 2017 CHAPTER 1 WPB AMENDMENTS
 FRAMING TYPE (WOOD, METAL)?
 FRAMING SPACING O.C.
 SHEATHING Y/N AND IS YES WHAT THICKNESS
  
 2) PLEASE SHOW LATH FASTENERS TO COMPLY WITH R703.7.1
  
 3) FBC R703.7.2 PLASTER.
 PLASTERING WITH CEMENT PLASTER SHALL BE NOT LESS THAN
 THREE COATS WHERE APPLIED OVER ANY TYPE OF
 CODE-APPROVED LATH AND SHALL BE NOT LESS THAN TWO COATS
 WHERE DIRECTLY APPLIED OVER MASONRY, CONCRETE, CLAY
 BRICK, STONE OR TILE. IF THE PLASTER SURFACE IS
 COMPLETELY COVERED BY VENEER OR OTHER FACING MATERIAL
 OR IS COMPLETELY CONCEALED, PLASTER APPLICATION NEED BE
 ONLY TWO COATS, PROVIDED THE TOTAL THICKNESS IS AS SET
 FORTH IN TABLE R702.1(1).
  
  
  