| Plan Review Notes For Permit 22101432 |
| Permit Number |
22101432 |
|
| Review Stop |
PW |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-28 10:36:01 | THE REVISED SITE DETAIL, SHEET AS101, STILL DOES NOT | | | FULLY COMPLY WITH OUR REQUIREMENTS ATTACHED. BELOW ARE | | | LIST OF NON-COMPLIANT ISSUES: | | | 1. BOLLARD GROUP FILLED NOT ACCEPTABLE (STOP BAR IS | | | REQUIRED) | | | 2. CONCRETE PAD SLOPE (SHALL HAVE POSITIVE SLOPE FOR | | | RAIN TO DRAIN AWAY FROM THE ENCLOSURE) | | | 3. WALLS MUST BE LANDSCAPED WITH HEDGE MATERIAL AT 2 FT | | | INTERVALS | | | 4. EACH DOOR SHALL BE EQUIPPED WITH A PIN TO HELP | | | SECURE THE DOOR WHEN OPENED | | | 5. MIN. 3-INCH DEEP PIN HOLES NEEDED IN THE ASPHALT FOR | | | EACH DOOR TO HELP SECURE THE DOORS WHEN FULLY OPENED AT | | | A 90+ DEG. ANGLE | | | 6. DOORS SHALL BE HINGED FROM OUTSIDE | | | 7. ALL HARDWARE TO BE HOT DIPPED GALVANIZED | | | |
|