| Plan Review Notes For Permit 22101425 |
| Permit Number |
22101425 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-10 10:42:13 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 22101425, 22101430 | | | 3/10/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P202: SHOW THE NEW DRINKING FOUNTAIN DRAIN AND | | | VENT PIPE RUNS ON THE PLANS AND PROVIDE A SANITARY | | | RISER DRAWING- SECS. 107.2.1 & 107.3.5.1.3 WPB. | | | | | | 2) SHEET A204: THE REVISED SHEET SHOWS NEW ACCESSIBLE | | | DRINKING FOUNTAINS ON THE EXTERIOR OF THE BUILDING THAT | | | APPEAR TO BE PROTRUDING OBJECTS IN THE CIRCULATION | | | PATH- SEE SEC. 307.2 FBC ACC. IT APPEARS THE FOUNTAINS | | | WILL HAVE TO BE RELOCATED AND RECESSED IN A NICHE, OR | | | GUARDS WILL HAVE TO BE INSTALLED AT THE CURRENT | | | LOCATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|