Plan Review Notes
Plan Review Notes For Permit 22101425
Permit Number 22101425
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2023-03-10 09:21:39FIRE PROVISO COMMENTS:
  
 (1) PROVIDE ADEQUATE CODE COMPLIANT PORTABLE FIRE
 EXTINGUISHER COVERAGE SO THAT THE NEAREST PORTABLE FIRE
 EXTINGUISHER DOES MOT EXCEED 75 FEET (I.E. LAUNDRY
 ROOM, COMMUNITY/OFFICE BUILDING)
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE PROTECTED FROM DAMAGE INCLUDING
 PAINTING DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (5) ANY WORK, CHANGES, MODIFICATIONS, ADDITIONS,
 DELETIONS, ETC. OF ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  