| Date |
Text |
| 2023-03-15 14:55:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22101425 |
| | ADD: 550, 580 EXECUTIVE CENTER DR. |
| | |
| | W. P. B. PERMIT: 22101430 |
| | ADD: 540 EXECUTIVE CENTER DR. |
| | |
| | CONT: LEGACY CONSTRUCTION SERVICES, INC. |
| | TEL: 216-297-2170 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 25/2023 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. PERMIT 22101425. SHEET G103 BUILDING CODE |
| | DATA, LEASING / COMMUNITY OFFICE FLOOR PLAN. |
| | |
| | |
| | 2) COMPLIED. |
| | |
| | 3) COMPLIED. SHEET A900. 2020 FBC-B 1603.1.4 WIND |
| | DESIGN CRITERIA. |
| | |
| | 4A) SEMI-COMPLIED. IN THE FILE FOLDER THE PGT PATIO |
| | DOORS DID-NOT LOAD. |
| | SHEET 540 & 580 FLOOR PLANS. NOTE # 1 REMOVE AND |
| | REPLACE VINYL WINDOWS AND EXTERIOR DOORS. NOTE # 5 TO |
| | REMOVE & REPLACE ALL EXTERIOR DOORS. COMPONENTS & |
| | CLADDING. PLEASE SUBMIT THE COMPONENTS AND CLADDING |
| | PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | PGT PATIO DOORS DID NOT LOAD, WILL NOT OPEN FOR REVIEW |
| | NO EXTERIOR SWING DOORS WERE SUBMITTED. |
| | (B) WINDOWS & MULLIONS |
| | PGT HORIZONTAL ROLLERS NOA-20-0406.01 THE NOA IS NOT |
| | HIGHLIGHTED AS REQUESTED COMMENT 4F. |
| | PGT SINGLE HUNG WINDOW NOA 20-0401.03 IS NOT |
| | HIGHLIGHTED AS REQUESTED COMMENT 4F. |
| | SHEET A-900 DETAILS 8 & 9 SHOW WINDOWS BUT THEY DO NOT |
| | STATE IF THEY ARE HORIZONTAL SLIDERS OR 2 SINGLE HUNG |
| | WINDOWS REQUIRING MULLIONS. |
| | (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS |
| | SYSTEMS, |
| | |
| | 4B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 4C) NOTICE ONLY: DELEGATED ENGINEERING. 61G15-30.003 |
| | ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 4D) NON-COMMENT SUBMITTED COMPONENT & CLADDING PRODUCT |
| | APPROVALS. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 4E) 2ND REQUEST, PGT PATIO DOOR PRODUCT APPROVAL DID |
| | NOT OPEN WILL NEED REVIEW FOR PRESSURES AND SILL |
| | HEIGHT, FOR POSITIVE PRESSURES. |
| | 1ST ROUND OF COMMENTS. 2020 FBC-B 1709.5.1 HABITAT |
| | SPACES, WATER INTRUSION. EXTERIOR DOORS AND WINDOWS. |
| | EXCEPTION # 2. SILL LIMITING FACTOR. |
| | |
| | 4F) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL |
| | HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 5) COMPLIED NOT APPLICABLE. |
| | |
| | 6A) SEMI-COMPLIED.A-900 DOOR SCHEDULE NOW SHOWS METAL |
| | LOUVER DOOR BUT STILL HAS WOOD FRAME, EITHER METAL |
| | FRAME OR DRYWALL WITH BEADS AND DRYWALL MUD. |
| | 1ST ROUND OF COMMENTS. THIS COMMENT FOR 540 & 580 ALL |
| | FLOORS AND UNITS. THE AIR HANDLER/ WATER HEATER CLOSET |
| | SHEET M-200 SHOWS THE REPLACEMENT OF AIR HANDLER, A |
| | VERTICAL UNIT W/ WATER HEATER BELOW. SHEET A200 NOTE 7 |
| | STATES TO REPLACE THE WATER HEATER. SHEET A200 DOOR FOR |
| | THE MECHANICAL CLOSET IS LABELED DOOR TYPE 7. SHEET |
| | A-900 DOOR AND WINDOW SCHEDULE DOOR TYPE 7 IS A WOOD |
| | LOUVERED BI-FOLD DOOR. SINCE THERE IS NO DIRECT RETURN, |
| | THE SPACE WITHIN THE MECHANICAL CLOSET IS CONSIDERED A |
| | PLENUM, NO COMBUSTIBLES ARE ALLOWED IN A PLENUM. PLEASE |
| | REVIEW IN THE 2020 FBC-MECHANICAL CODE SECTIONS 602.2 |
| | CONSTRUCTION & 602.2.1 MATERIALS WITHIN PLENUMS. METAL |
| | BI-FOLD DOORS ARE ACCEPTABLE. |
| | |
| | 6B) SHEET A-203. THE MECHANICAL CLOSET VERTICAL A/C AIR |
| | HANDLER AND WATER HEATER TO BE REPLACED. DOOR TO |
| | MECHANICAL CLOSET IS IDENTIFIED AS #8. SHEET A-900 TYPE |
| | F IS A WOOD HOLLOW CORE BI-FOLD DOOR. SINCE THERE IS NO |
| | DIRECT RETURN, THE SPACE WITHIN THE MECHANICAL CLOSET |
| | IS CONSIDERED A PLENUM, NO COMBUSTIBLES ARE ALLOWED IN |
| | A PLENUM. PLEASE REVIEW IN THE 2020 FBC-MECHANICAL CODE |
| | SECTIONS 602.2 CONSTRUCTION & 602.2.1 MATERIALS WITHIN |
| | PLENUMS. METAL BI-FOLD DOORS ARE ACCEPTABLE. PLEASE |
| | ALSO NOTE THAT THE VERTICAL AIR HANDLER WOULD HAVE TO |
| | SIT ON A METAL STAND NOT WOOD FRAMING. |
| | |
| | 7) SHEET A-204 COMMON AREA ENLARGED FLOOR PLAN AND |
| | ELEVATIONS 2020 FBC-ACCESSIBILITY CODE: |
| | |
| | 7A) 2ND REQUEST. DETAILS 4 & 10 PLEASE REVIEW TOILET |
| | PAPER DISPENSERS. 604.7. THE TOILET PAPER DISPENSER |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| | |
| | 7B) 2ND REQUEST. THE SIDE GRAB BARS ARE NOT DIMENSIONED |
| | FROM THE CORNER WALL. 2020 FBC-ACCESSIBILITY CODE |
| | SECTION 604.5.1 THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL. |
| | |
| | 7C) 2ND REQUEST, DRAINPIPES NOT SHOWN, WALL HUNG |
| | LAVATORY DOES NOT SHOW WASTE PIPES NOR 606.5 EXPOSED |
| | PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER |
| | LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| | CONFIGURED TO PROTECT AGAINST CONTACT. |
| | |
| | 7D) COMPLIED. DETAIL # 12 THE KITCHENETTE SHOWS THE |
| | HEIGHT TO THE TOP OF THE BACK SPLASH TO BE 2FEET 10 |
| | INCHES, NOT TO THE COUNTERTOP. SINKS> 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES |
| | AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE |
| | HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 7E)2ND REQUEST. FLOOR PLAN IS MISSING THE REQUIRED |
| | CLEAR FLOOR SPACE. 606.2 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT |
| | SHOW THE REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN. |
| | |
| | 7F) THE FLOOR PLAN SHOWS A SINGLE DRINKING FOUNTAIN. |
| | THE 2020 EXISTING BUILDING CODE LEVEL I, LEVEL 2 OR |
| | LEVEL 3 ALL REFER YOU TO THE 2020 FBC-ACCESSIBILITY |
| | CODE. FLORIDA ACCESSIBILITY CODE SECTION: |
| | DISPROPORTIONATE COST 202.4.1. PART OF THE UPGRADES |
| | WOULD INCLUDE: |
| | |
| | 7F)(1-2) COMPLIED. |
| | 7F)(3) 2ND REQUEST. 602.2 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | |
| | 7F)(4) 2ND REQUEST. SPOUT OUTLETS/ DRINKING FOUNTAINS. |
| | 2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND |
| | INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |