Plan Review Notes
Plan Review Notes For Permit 22101425
Permit Number 22101425
Review Stop E
Sequence Number 1
Notes
Date Text
2023-01-10 09:18:31ELECTRIC REVIEW FAILED
 1) PLANS STATE NO GAS APPLIANCES WILL BE PRESENT IN
 BUILDING AND THAT ONLY SMOKE ALARMS ARE NEEDED.
 HOWEVER, PLUMBING PLAN DETAILS BY NOTE THAT WATER
 HEATERS ARE GAS. PLEASE PROVIDE CLARIFICATION, AND IF
 ANY GAS APPLIANCES ARE PRESENT PLEASE PROVIDE CARBON
 MONOXIDE ALARMS AS WELL AS SMOKE ALARMS. FBC 107.2 AND
 FBC R315.1
 2) PLEASE PROVIDE A NOTE ON PLANS STATING FIRE ALARM,
 ACCESS CONTROL, VOICE, DATA, SECURITY, AUDIO, VIDEO OR
 OTHER LOW VOLTAGE WIRING SYSTEMS REQUIRE SEPARATE
 PERMITS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  