| Date |
Text |
| 2022-12-19 16:33:36 | FAILED |
| | |
| | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY (22040938) MUST BE APPROVED |
| | PRIOR TO THIS PERMIT BEING APPROVED. SOME OF THE |
| | COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT |
| | REVIEW AS WELL AS WITH THIS PERMIT. |
| | |
| | 2) NO SURVEY WAS PROVIDED WITH THIS PERMIT. PLEASE |
| | INCLUDE THE SURVEY (AND OTHER RELEVANT PLANS) INCLUDED |
| | WITH THE WCF PERMIT. |
| | |
| | 3) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE |
| | POWER POLE THAT WILL SUPPLY THE UNDERGROUND POWER ON |
| | PRIVATE PROPERTY AND REQUIRING A CROSSING OF THE |
| | PRIVATE PROPERTY TO REACH THE HANDHOLE AT STA 0+00. IN |
| | ORDER FOR THE UNDERGROUND ELECTRIC TO CROSS PRIVATE |
| | PROPERTY, IT MUST BE LOCATED WITHIN A GENERAL UTILITY |
| | EASEMENT. THE SURVEY DOES NOT SHOW AN EASEMENT AT THIS |
| | LOCATION. IF THERE IS AN EASEMENT, IT MUST BE SHOWN ON |
| | THE SURVEY AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE |
| | SHOWN IN THE EASEMENT. IF NO EASEMENT IS PRESENT, THE |
| | UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE |
| | LOCATION. |
| | |
| | 4) THE SURVEY PROVIDED WITH THE WCF PERMIT SHOWS THE |
| | FULL LENGTH OF THE POWER ROUTE, TO INCLUDE THE |
| | HANDHOLES AND BORE PITS, IS LOCATED WITHIN THE |
| | RIGHT-OF-WAY, HOWEVER, THE LOCATION OF THE GAS LINE AT |
| | STA 0+00 IS NOT SHOWN AT THE SAME LOCATION ON THE |
| | SURVEY AND SHEET E101. BASED ON THE SURVEY, THERE IS A |
| | DIRECT CONFLICT WITH THE HANDHOLE AND ITS EXCAVATION |
| | AND THE GAS LINE. YOU NEED TO PROVIDE VERIFICATION FROM |
| | FPU THAT THEY DO NOT OBJECT TO THE PROPOSED |
| | INSTALLATION LOCATION OF YOUR FACILITIES. |
| | |
| | 5) THE LAT/LON FOR THE POLE ON THE SURVEY AND SITE PLAN |
| | IS SHOWN AS THE HANDHOLE LOCATION ON THE POWER ROUTE |
| | PLAN. PLEASE ENSURE THAT ALL PLANS ARE LABELED |
| | CORRECTLY. |
| | |
| | 6) THE NEWLY UPLOADED SHEET E201 DOES NOT SHOW A POLE |
| | THAT MEETS THE CITY'S STEALTH REQUIREMENTS. THE |
| | ORIGINAL SUBMITTAL SHOWED A COMPLIANT POLE DESIGN. |
| | SHEETS A201 AND A502 PROVIDED WITH THE WCF PERMIT SHOW |
| | A COMPLIANT POLE. |
| | |