Plan Review Notes
Plan Review Notes For Permit 22101334
Permit Number 22101334
Review Stop B
Sequence Number 3
Notes
Date Text
2022-12-19 12:11:34JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5680-R35 HAS BEEN REVISED TO FL5680-R36.
 PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION
 REPORT PAGES 1-6 AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5680-R36 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM TYPE A1-F NO. W-1 THRU W-74.
 SELECTED SYSTEM TYPE TO BE USED THAT MEET THE MINIMUM
 ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 FOR
 EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT MEETS OR
 EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR EXPOSURE
 CATEGORY C/PROVIDE SIGNED AND SEALED ENGINEERED NAILING
 CALCULATIONS WITH AN APPROVED SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  