| 2022-11-14 15:57:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22101289 1920 WEKIVA WAY |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL. |
| | |
| | 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW BREAK ROOM INDICATING THE FOLLOWING: |
| | ***A) TOE AND KNEE CLEARANCE FOR SINK AS REQUIRED BY |
| | FBC ACC 306.2 AND 306.3; INCLUDE UNDERCOUNTER WATER |
| | HEATER TO SHOW THAT IT WILL NOT ADVERSELY AFFECT THE |
| | ACCESSIBILITY. |
| | ***B) CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 |
| | POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE |
| | SINK |
| | |
| | 2. WORK APPEARS TO TAKE PLACE ON THE GROUND FLOOR. PER |
| | WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON THE |
| | PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | 3. A13.0 INTERIOR SCHEDULE INDICATES MOTHER'S ROOM WITH |
| | LAVATORY. NOTHING SHOWN ON THE PLANS. PER WPB FBC |
| | 107.2.1, PLEASE CLARIFY. |
| | |
| | 4. P1.01/WATER HEATER DETAIL: FBC PL 606.1 AND 503.1, |
| | PROVIDE DEDICATED SHUT OFF VALVE FOR COLD WATER TO |
| | FAUCET AND FOR COLD WATER TO WATER HEATER. |
| | |
| | 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR |
| | CONFORMING TO ASSE 1010 AT MOISTURE SENSING SOLENOID |
| | VALVE. |
| | |
| | 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3 (2), TO SHOW |
| | COMPLIANCE WITH FBC PL 403.1, TABLE 403.1, PROVIDE |
| | LOCATION OF SERVICE SINK. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM |
| | WHEN RESUBMITTING. |
| | |