2022-11-14 15:57:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22101289 1920 WEKIVA WAY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW BREAK ROOM INDICATING THE FOLLOWING:
 ***A) TOE AND KNEE CLEARANCE FOR SINK AS REQUIRED BY
 FBC ACC 306.2 AND 306.3; INCLUDE UNDERCOUNTER WATER
 HEATER TO SHOW THAT IT WILL NOT ADVERSELY AFFECT THE
 ACCESSIBILITY.
 ***B) CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE
 SINK
  
 2. WORK APPEARS TO TAKE PLACE ON THE GROUND FLOOR. PER
 WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON THE
 PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 3. A13.0 INTERIOR SCHEDULE INDICATES MOTHER'S ROOM WITH
 LAVATORY. NOTHING SHOWN ON THE PLANS. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
  
 4. P1.01/WATER HEATER DETAIL: FBC PL 606.1 AND 503.1,
 PROVIDE DEDICATED SHUT OFF VALVE FOR COLD WATER TO
 FAUCET AND FOR COLD WATER TO WATER HEATER.
  
 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 AT MOISTURE SENSING SOLENOID
 VALVE.
  
 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3 (2), TO SHOW
 COMPLIANCE WITH FBC PL 403.1, TABLE 403.1, PROVIDE
 LOCATION OF SERVICE SINK.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM
 WHEN RESUBMITTING.
  