| Plan Review Notes For Permit 22101289 |
| Permit Number |
22101289 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-16 10:45:08 | 1ST REVIEW FMC | | | PERMIT: 22101289 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH | | | USE OF SPACE, OCCUPANCY CLASSIFICATION FROM FMC TABLE | | | 403.3.1.1. FMC 403.3.1.1 | | | | | | 2) EXPLAIN THE PRODUCTION ROOM USE AND PROVIDE THE | | | OCCUPANCY CLASSIFICATION FOR THIS AREA. FMC 403.3.1.1 | | | | | | 3) SHEET M1.01: AHU-1APPEARS TO CONDITION THE RECEPTION | | | AREA AND THE CONFERENCE ROOM AND THEN GO INTO AN AREA | | | THAT ISN???T COVERED UNDER THIS PERMIT. IS THIS AREA A | | | DIFFERENT TENANT SPACE? | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|