| Date |
Text |
| 2023-05-10 14:03:55 | WINDOWS AND DOORS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) AN EXHAUST SYSTEM WILL BE REQUIRED FOR THE BATHROOM |
| | - FBC R303.3 BATHROOMS. |
| | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR |
| | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN |
| | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), |
| | ONE-HALF OF WHICH MUST BE OPENABLE. |
| | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE |
| | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE |
| | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST |
| | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE |
| | OUTDOORS. |
| | |
| | 2) PLEASE REVISE THE BUILDING PERMIT APPLICATION TO |
| | SHOW THE JOB VALUE THAT INCLUDES THE LABOR COST - |
| | WINDOW ESTIMATE PROVIDED SHOWS ONLY THE COST OF THE |
| | WINDOWS - FBC 109.3 BUILDING PERMIT VALUATION. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL ??? SWIFT, MEANS, ETC.) AS PUBLISHED |
| | BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |