Plan Review Notes
Plan Review Notes For Permit 22101241
Permit Number 22101241
Review Stop P
Sequence Number 3
Notes
Date Text
2023-01-25 14:58:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22101241 150 CLEARWATER DR
  
 3RD REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW
 PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
 PLEASE PROVIDE PERMIT NUMBER IF PERMIT HAS BEEN
 GENERATED TO [email protected]
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOMS INDICATING THE FOLLOWING:
 THIRD REQUEST:***B) CLEARANCE AROUND A WATER CLOSET
 SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG
 WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR
 MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE
 REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1
 PLUMBING FIXTURE SCHEDULE INDICATES FLOOR MOUNTED WATER
 CLOSETS: CLEARANCE SHALL BE 59 INCHES DEEP MINIMUM. FBC
 ACC 604.8.1.1
  
 RPJ RESPONSE: SEE A0-004, A1-402 A1-403.
  
 ALL SHOW 56 INCHES, NOT 59 INCHES AS REQUIRED BY FBC
 ACC 604.1.1
  
  
 2. PARTIALLY COMPLIED: P1-302/SANITARY RISERS-VENTS;
 PLEASE PROVIDE VENT INFRASTRUCTURE TO SERVICE PRESENT
 AND FUTURE VENT CONNECTIONS. INDICATE SIZES, HOW AND
 WHERE SANITARY VENTS WILL TERMINATE. FBC PL SECTIONS
 903, 906
 RPJ RESPONSE: VENT, SANITARY AND WATER HAVE BEEN ADDED
 TO SHEETS P1-201A THROUGH P1-203B.
  
 NEW COMMENT: PLANS NOW INDICATE VENTS TO SERVICE
 SANITARY BUT DO NOT ADDRESS HOW AND WHERE SANITARY
 VENTS WILL TERMINATE AND THE SIZING OF THE VENTS.
 PLEASE PROVIDE. FBC PL SECTIONS 903, 906
  
  
 3. NEW COMMENT: GROUND FLOOR BATHROOMS ADJACENT TO
 BICYCLE STORAGE; OCCUPANCY CLASSIFICATION STORAGE
 (REVISED A1-402). A SERVICE SINK IS REQUIRED. FBC PL
 TABLE 403.1
  
  
 4. NEW COMMENT: P1-301/SECOND FLOOR WOMEN'S BATHROOM:
 WATER SUPPLY TO EACH OF TWO (2) P-1 WATER CLOSET SHALL
 BE MINIMUM 1 INCH. SEE P1-402 PLUMBING FIXTURE
 SCHEDULE. FBC PL TABLE 604.5
  
  
 5. NEW COMMENT: P1-202B, P1-303B, P1-304A
 AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON
 THE SOUTH GARAGE SECOND FLOOR (P1-202B) CONNECTING TO
 BRANCH SERVICING RWL 12, 16 ARE DISCHARGING AN
 ADDITIONAL 395 GPM TO THE BRANCH AND RWL 11. THIS
 INCREASE IN VOLUME IS NOT REFLECTED ON P1-303B AND
 P1-304A.
 AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON
 THE SOUTH GARAGE SECOND FLOOR (P1-202B) ARE DISCHARGING
 AN ADDITIONAL 395 GPM TO RWL 1,2. THIS INCREASE IN
 VOLUME IS NOT REFLECTED ON P1-303B AND P1-304A.
 MAKE CORRECTIONS ON DRAWINGS TO REFLECT AND UPDATE
 SIZING AS REQUIRED. FBC PL 1106.1
  
 6. NEW COMMENT: P1-202C, P1-201C
 PLEASE SIZE HORIZONTAL PIPING FOR AREA DRAINS AND
 PLANTER DRAINS ON THE SOUTH GARAGE SECOND FLOOR
 (P1-202C) AND THE HORIZONTAL UNDERGROUND STORM DRAIN TO
 CATCH BASIN (P201C). FBC PL 1106.1
  
  
 7. THIRD REQUEST: RPJ RESPONSE: NOTE FOR NOT TO EXCEED
 2 FT CAN BE FOUND ALREADY IN SHEET P1-3.01 NEXT TO BOTH
 BATHROOM ISOMETRICS. THERE ARE NO RECIRCULATION
 SYSTEMS.
  
 TO BE CLEAR, NOTE NOT TO EXCEED 2 FT DOES NOT ADDRESS
 THE ISSUE. IN ORDER TO COMPLY WITH FBC EC C404.5.1,
 TABLE C404.5.1, THE 1/2 INCH WATER LINE CANNOT EXCEED A
 DEVELOPED LENGTH OF 2 FEET FROM THE PUBLIC LAVATORY TO
 THE SOURCE OF HOT WATER. THE SOURCE WOULD BE THE WATER
 HEATER, A RECIRCULATING PIPING SYSTEM OR HEAT TRACED
 PIPING. FBC PL 607.2
 PLEASE PROVIDE AN ACCEPTABLE PIPING METHOD TO
 ACCOMPLISH THIS. PROVIDE INSULATION FOR SYSTEM (COMPLY
 WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10) AND IF
 RECIRCULATING, ADJUST WATER HEATER DETAIL AND PIPING
 PLAN TO REFLECT. INCLUDE RECIRC PUMP SCHEDULE IF
 APPLICABLE
  
  
 9. SECOND REQUEST: PLEASE PROVIDE SIZING FOR CD
 (CONDENSATE DRAINS). FBC PL 314.2.2.
 RPJ RESPONSE: SIZING FOR CD SYSTEM HAS BEEN ADDED TO
 SHEETS P1-201A THROUGH P1-201C.
  
 TO BE CLEAR, UNDERGROUND CONDENSATE DRAINS FROM RISERS
 TO CATCH BASINS ARE NOT SIZED. P1-201A, P1-201C
  
  
 10. PARTIALLY COMPLIED: PLEASE PROVIDE CONDENSATE
 DRAINS FOR FCUS NOTRD ON P1-201B, P1-201C. FBC PL 314.2
 RPJ RESPONSE: REQUIRED CONDENSATE DRAWINGS WERE ADDED
 THROUGH OUT
  
 SEE P1-201C/ELEVATOR LOBBY FCU-1-3 AND PROVIDE DRAIN.
  
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER
 ADDRESSING EACH ITEM.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  