| 2023-01-25 14:58:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22101241 150 CLEARWATER DR |
| | |
| | 3RD REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW |
| | PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS |
| | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN |
| | PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY |
| | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER(S). |
| | PLEASE PROVIDE PERMIT NUMBER IF PERMIT HAS BEEN |
| | GENERATED TO [email protected] |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOMS INDICATING THE FOLLOWING: |
| | THIRD REQUEST:***B) CLEARANCE AROUND A WATER CLOSET |
| | SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG |
| | WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR |
| | MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE |
| | REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1 |
| | PLUMBING FIXTURE SCHEDULE INDICATES FLOOR MOUNTED WATER |
| | CLOSETS: CLEARANCE SHALL BE 59 INCHES DEEP MINIMUM. FBC |
| | ACC 604.8.1.1 |
| | |
| | RPJ RESPONSE: SEE A0-004, A1-402 A1-403. |
| | |
| | ALL SHOW 56 INCHES, NOT 59 INCHES AS REQUIRED BY FBC |
| | ACC 604.1.1 |
| | |
| | |
| | 2. PARTIALLY COMPLIED: P1-302/SANITARY RISERS-VENTS; |
| | PLEASE PROVIDE VENT INFRASTRUCTURE TO SERVICE PRESENT |
| | AND FUTURE VENT CONNECTIONS. INDICATE SIZES, HOW AND |
| | WHERE SANITARY VENTS WILL TERMINATE. FBC PL SECTIONS |
| | 903, 906 |
| | RPJ RESPONSE: VENT, SANITARY AND WATER HAVE BEEN ADDED |
| | TO SHEETS P1-201A THROUGH P1-203B. |
| | |
| | NEW COMMENT: PLANS NOW INDICATE VENTS TO SERVICE |
| | SANITARY BUT DO NOT ADDRESS HOW AND WHERE SANITARY |
| | VENTS WILL TERMINATE AND THE SIZING OF THE VENTS. |
| | PLEASE PROVIDE. FBC PL SECTIONS 903, 906 |
| | |
| | |
| | 3. NEW COMMENT: GROUND FLOOR BATHROOMS ADJACENT TO |
| | BICYCLE STORAGE; OCCUPANCY CLASSIFICATION STORAGE |
| | (REVISED A1-402). A SERVICE SINK IS REQUIRED. FBC PL |
| | TABLE 403.1 |
| | |
| | |
| | 4. NEW COMMENT: P1-301/SECOND FLOOR WOMEN'S BATHROOM: |
| | WATER SUPPLY TO EACH OF TWO (2) P-1 WATER CLOSET SHALL |
| | BE MINIMUM 1 INCH. SEE P1-402 PLUMBING FIXTURE |
| | SCHEDULE. FBC PL TABLE 604.5 |
| | |
| | |
| | 5. NEW COMMENT: P1-202B, P1-303B, P1-304A |
| | AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON |
| | THE SOUTH GARAGE SECOND FLOOR (P1-202B) CONNECTING TO |
| | BRANCH SERVICING RWL 12, 16 ARE DISCHARGING AN |
| | ADDITIONAL 395 GPM TO THE BRANCH AND RWL 11. THIS |
| | INCREASE IN VOLUME IS NOT REFLECTED ON P1-303B AND |
| | P1-304A. |
| | AREA DRAINS AND PLANTER DRAINS THAT HAVE BEEN ADDED ON |
| | THE SOUTH GARAGE SECOND FLOOR (P1-202B) ARE DISCHARGING |
| | AN ADDITIONAL 395 GPM TO RWL 1,2. THIS INCREASE IN |
| | VOLUME IS NOT REFLECTED ON P1-303B AND P1-304A. |
| | MAKE CORRECTIONS ON DRAWINGS TO REFLECT AND UPDATE |
| | SIZING AS REQUIRED. FBC PL 1106.1 |
| | |
| | 6. NEW COMMENT: P1-202C, P1-201C |
| | PLEASE SIZE HORIZONTAL PIPING FOR AREA DRAINS AND |
| | PLANTER DRAINS ON THE SOUTH GARAGE SECOND FLOOR |
| | (P1-202C) AND THE HORIZONTAL UNDERGROUND STORM DRAIN TO |
| | CATCH BASIN (P201C). FBC PL 1106.1 |
| | |
| | |
| | 7. THIRD REQUEST: RPJ RESPONSE: NOTE FOR NOT TO EXCEED |
| | 2 FT CAN BE FOUND ALREADY IN SHEET P1-3.01 NEXT TO BOTH |
| | BATHROOM ISOMETRICS. THERE ARE NO RECIRCULATION |
| | SYSTEMS. |
| | |
| | TO BE CLEAR, NOTE NOT TO EXCEED 2 FT DOES NOT ADDRESS |
| | THE ISSUE. IN ORDER TO COMPLY WITH FBC EC C404.5.1, |
| | TABLE C404.5.1, THE 1/2 INCH WATER LINE CANNOT EXCEED A |
| | DEVELOPED LENGTH OF 2 FEET FROM THE PUBLIC LAVATORY TO |
| | THE SOURCE OF HOT WATER. THE SOURCE WOULD BE THE WATER |
| | HEATER, A RECIRCULATING PIPING SYSTEM OR HEAT TRACED |
| | PIPING. FBC PL 607.2 |
| | PLEASE PROVIDE AN ACCEPTABLE PIPING METHOD TO |
| | ACCOMPLISH THIS. PROVIDE INSULATION FOR SYSTEM (COMPLY |
| | WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10) AND IF |
| | RECIRCULATING, ADJUST WATER HEATER DETAIL AND PIPING |
| | PLAN TO REFLECT. INCLUDE RECIRC PUMP SCHEDULE IF |
| | APPLICABLE |
| | |
| | |
| | 9. SECOND REQUEST: PLEASE PROVIDE SIZING FOR CD |
| | (CONDENSATE DRAINS). FBC PL 314.2.2. |
| | RPJ RESPONSE: SIZING FOR CD SYSTEM HAS BEEN ADDED TO |
| | SHEETS P1-201A THROUGH P1-201C. |
| | |
| | TO BE CLEAR, UNDERGROUND CONDENSATE DRAINS FROM RISERS |
| | TO CATCH BASINS ARE NOT SIZED. P1-201A, P1-201C |
| | |
| | |
| | 10. PARTIALLY COMPLIED: PLEASE PROVIDE CONDENSATE |
| | DRAINS FOR FCUS NOTRD ON P1-201B, P1-201C. FBC PL 314.2 |
| | RPJ RESPONSE: REQUIRED CONDENSATE DRAWINGS WERE ADDED |
| | THROUGH OUT |
| | |
| | SEE P1-201C/ELEVATOR LOBBY FCU-1-3 AND PROVIDE DRAIN. |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER |
| | ADDRESSING EACH ITEM. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |