2023-01-31 06:22:08THE ENCLOSED PARKING GARAGE SHALL MEET FMC 404.1 BELOW.
 THE FANS SHALL NOT BE OFF.
  
 404.1 ENCLOSED PARKING GARAGES. MECHANICAL VENTILATION
 SYSTEMS FOR ENCLOSED PARKING GARAGES SHALL OPERATE
 CONTINUOUSLY OR SHALL BE AUTOMATICALLY OPERATED BY
 MEANS OF CARBON MONOXIDE DETECTORS APPLIED IN
 CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS. CARBON
 MONOXIDE DETECTORS SHALL BE INSTALLED 3 TO 5 FEET ABOVE
 FLOOR LEVEL AND NITROGEN DIOXIDE DETECTORS SHALL BE
 INSTALLED 1 FOOT BELOW CEILING LEVEL. SUCH DETECTORS
 SHALL BE LISTED IN ACCORDANCE WITH UL 2075 AND
 INSTALLED IN ACCORDANCE WITH THEIR LISTING AND THE
 MANUFACTURERS??? INSTRUCTIONS. AUTOMATIC OPERATION
 SHALL CYCLE THE VENTILATION SYSTEM BETWEEN THE
 FOLLOWING TWO MODES OF OPERATION:
  
 1. FULL-ON AT AN AIRFLOW RATE OF NOT LESS THAN 0.75 CFM
 PER SQUARE FOOT OF THE FLOOR AREA SERVED.
  
 2. STANDBY AT AN AIRFLOW RATE OF NOT LESS THAN 0.05 CFM
 PER SQUARE FOOT OF THE FLOOR AREA SERVED.
  