| 2023-01-27 15:42:35 | 9 STORY PARKING GARAGE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) THE THRESHOLD FORM PROVIDED IS FOR A DIFFERENT CITY |
| | - THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED TO |
| | BE FILLED OUT - PLEASE READ AND FILL OUT THE REQUIRED |
| | DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING THRESHOLD/SPECIAL INSPECTORS AND RESIDENT |
| | INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A COPY. |
| | |
| | 2) DRAWING A0-002 THE PARKING CALCS. SAY 4 ACCESSIBLE |
| | PARKING SPACES FOR THE GROUND FLOOR - DRAWING A1-101 |
| | SHOWS 6 PLEASE CLARIFY - ARE ALL ACCESSIBLE SPACES ON |
| | ALL FLOORS "VAN" ACCESSIBLE? |
| | |
| | 3) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO |
| | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT |
| | SHOWS THE REQUIRED WIND DESIGN PRESSURE - PLEASE CIRCLE |
| | THE ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL - |
| | IF NEEDED PLEASE PROVIDE ADDITIONAL ATTACHMENT DETAILS |
| | FROM AN ARCHITECT OR ENGINEER FOR THE ROOF ZONES 2 AND |
| | 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE THEN THE |
| | CHOSEN ROOFING SYSTEM - SEE NOTES ON THE PRODUCT |
| | APPROVAL. |
| | |
| | 4) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE LIGHT |
| | WEIGHT CONCRETE - FBC 1917.2.1 |
| | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF |
| | DECKS SHALL BE BY APPLICATORS APPROVED BY THE |
| | LIGHT-WEIGHT INSULATING CONCRETE DECK MANUFACTURER. |
| | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT |
| | INSULATING CONCRETE SYSTEMS. |
| | |
| | |
| | |