| 2023-01-04 14:09:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22101241 150 CLEARWATER DR |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW |
| | PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS |
| | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN |
| | PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY |
| | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER(S). |
| | NEW COMMENT: PLEASE PROVIDE PERMIT NUMBER IF PERMIT HAS |
| | BEEN GENERATED TO [email protected] |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOMS INDICATING THE FOLLOWING: |
| | SECOND REQUEST:***B) CLEARANCE AROUND A WATER CLOSET |
| | SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG |
| | WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR |
| | MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE |
| | REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1 |
| | PLUMBING FIXTURE SCHEDULE INDICATES FLOOR MOUNTED WATER |
| | CLOSETS: CLEARANCE SHALL BE 59 INCHES DEEP MINIMUM. FBC |
| | ACC 604.8.1.1 |
| | |
| | 2. SECOND REQUEST: PER WPB FBC 107.2.1, REGARDING PLAN |
| | SHEET A1-402, TO SHOW COMPLIANCE WITH FBC PL 403.1 AND |
| | TABLE 403.1, PROVIDE OCCUPANCY AND OCCUPANCY LOAD FOR |
| | THE BATHROOMS SERVICING THE NORTH GARAGE GROUND FLOOR. |
| | A0-403 ONLY ADDRESSES REQUIREMENTS FOR SECOND FLOOR |
| | RESTROOMS |
| | |
| | 3. COMPLIED |
| | |
| | 4. SECOND REQUEST: PLAN PAGES 262 P1-201A NORTH GARAGE |
| | GROUND FLOOR PLAN PLUMBING AND 114 C-15 WSU PLAN: |
| | SANITARY BUILDING DRAINS/BUILDING SEWERS DO NOT MATCH |
| | UP TO CIVIL CONNECTIONS. PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PLEASE CLARIFY AND RECONCILE. |
| | ITEM 4 IS NOT IN RESPONSE LETTER; NOTED AS ITEM 6 BUT |
| | NO RESPONSE IS GIVEN |
| | |
| | 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE |
| | SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE |
| | MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE |
| | RISER DIAGRAMS COMPLIED; RESPONSE NOTED AS ITEM 7 SEE |
| | P1-300 SERIES |
| | NEW COMMENT: P1-302/SANITARY RISERS; P-4 MOP SINK AT |
| | SECOND FLOOR BATHROOMS IS NOT INDICATED ON THE WATER |
| | RISER. PLEASE INDICATE. WPB FBC 107.2.1, 107.3.5.1.3 |
| | NEW COMMENT: P1-302/SANITARY RISERS-VENTS; PLEASE |
| | PROVIDE VENT INFRASTRUCTURE TO SERVICE PRESENT AND |
| | FUTURE VENT CONNECTIONS. INDICATE SIZES, HOW AND WHERE |
| | SANITARY VENTS WILL TERMINATE. FBC PL SECTIONS 903, 906 |
| | |
| | 6. COMPLIED |
| | 7. COMPLIED |
| | |
| | 8. COMPLIED: PER WPB FBC 107.2.1 AND 107.3.5.1.3, |
| | CALCULATIONS FOR STORM PIPING SHALL BE ACCUMULATED AND |
| | APPLIED TO SIZING OF ALL STORM PIPING TO INCLUDE |
| | VERTICAL CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, |
| | BUILDING STORM SEWERS AND ANY HORIZONTAL BRANCHES OF |
| | SUCH DRAINS OR SEWERS PER FBC PL 1106.1. |
| | CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL SURFACES |
| | AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4 |
| | ENGINEER RESPONSE: REFER TO SHEET P1-304A AND P1-304B |
| | FOR ALL |
| | CALCULATIONS. |
| | |
| | NEW COMMENT: PLEASE ADD NOTE TO P1-303A, P1-303B, |
| | P1-304A AND P1-304B STATING "PLEASE NOTE, PER WPB FBC |
| | 107.2.1 AND 107.3.5.1.3, CALCULATIONS FOR STORM PIPING |
| | SHALL BE ACCUMULATED AND APPLIED TO SIZING OF ALL STORM |
| | PIPING TO INCLUDE VERTICAL CONDUCTORS AND LEADERS, |
| | BUILDING STORM DRAINS, BUILDING STORM SEWERS AND ANY |
| | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS. PER FBC |
| | PL 1106.1. CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL |
| | SURFACES AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4. |
| | SEE P1-303A, P1-303B, P1-304A AND P1-304B. SEE |
| | P1-4.01/GENERAL PLUMBING NOTES SECTION 5/NOTE D FOR |
| | MINIMUM SLOPE OF 1/8 INCH PER FOOT FOR HORIZONTAL |
| | PIPING." |
| | |
| | 9. COMPLIED |
| | |
| | 10. SECOND REQUEST: PER WPB FBC 107.3.5.1.3, FBC PL |
| | 604.1, 604.3, PROVIDE CALCULATIONS FOR SIZING OF WATER |
| | DISTRIBUTION |
| | AT A MINIMUM PLEASE PROVIDE MAXIMUM GPM FOR GIVEN |
| | SIZES. |
| | |
| | 11. SECOND REQUEST: PER WPB FBC 107.3.5.1.3, FBC PL |
| | 710.1, PROVIDE CALCULATIONS FOR SIZING OF SANITARY |
| | DRAINAGE. |
| | IT IS NOTED THAT FIXTURE UNITS HAVE BEEN PROVIDED FOR |
| | BATHROOM PIPING. AT A MINIMUM, PLEASE PROVIDE MAXIMUM |
| | AMOUNT OF FIXTURE UNITS THAT MAY CONNECT TO GIVEN SIZES |
| | OF THE BUILDING DRAIN. |
| | |
| | 12. COMPLIED |
| | 13. COMPLIED |
| | |
| | 14. PARTIALLY COMPLIED: PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PLEASE PROVIDE A PLUMBING LEGEND; I.E., |
| | GD=?, FM=?, ETC. |
| | NEW COMMENT: P1-4.01; PLEASE AMEND DESCRIPTION OF "SD" |
| | LEGENDS TO READ STORM DRAIN/EXISTING STORM DRAIN, NOT |
| | GREASY WASTE/EXISTING GREASY WASTE |
| | |
| | 15. COMPLIED |
| | 16. COMPLIED |
| | 17. COMPLIED |
| | |
| | 18. SECOND REQUEST: P1-2.01A: SANITARY BRANCH FROM |
| | BATHROOMS ADJACENT TO BICYCLE PARKING SPACE IS SHOWN |
| | DISCHARGING INTO THE FM (FORCE MAIN?) FROM ELEVATOR |
| | SUMP PUMP AT GRID LINES G-13 AND THEN INTO HD (HUB |
| | DRAIN?) IS THIS BRANCH A SUBDRAIN UNABLE TO DRAIN BY |
| | GRAVITY INTO BUILDING DRAIN? IF SO, IT SHALL BE |
| | DISCHARGED INTO THE SANITARY BUILDING DRAIN IN |
| | ACCORDANCE WITH FBC PL 712.3.5, THROUGH A SEWAGE PUMP |
| | OR SEWAGE EJECTOR PER FBC PL 712.4. AN EQUIPMENT |
| | SCHEDULE/SPECIFICATION FOR PUMP AND SUMP WITH A DETAIL |
| | SHALL BE PROVIDED. IF NOT A SUBDRAIN THEN CONNECT |
| | DIRECTLY TO THE BUILDING DRAIN PER FBC PL 712.1, NOT TO |
| | THE FM (FORCE MAIN). |
| | NO RESPONSE INDICATED IN RESPONSE LETTER; PLEASE NOTE, |
| | NEW SHEET P1-302 ISOMETRIC INDICATES ELEVATOR SUMP PUMP |
| | DISCHARGING INDEPENDENTLY TO A HUB DRAIN WHICH IS |
| | COMPLIANT. |
| | THE SANITARY BRANCH FROM THE WOMEN???S BATHROOM IS |
| | SHOWN BUT THE POINT OF CONNECTION IS NOT SHOWN. PLEASE |
| | INDICATE THE CONNECTION TO THE SANITARY BUILDING DRAIN. |
| | IF THIS IS A SUB-DRAIN, DISCHARGE THROUGH A SEWAGE |
| | PUMP/EJECTOR TO THE SANITARY BUILDING DRAIN IN |
| | ACCORDANCE WITH FBC PL SECTION 712. IF NOT A SUBDRAIN |
| | THEN CONNECT BY GRAVITY DIRECTLY TO THE BUILDING DRAIN. |
| | IF SEWAGE PUMP IS REQUIRED PLEASE PROVIDE SPEC AND |
| | DETAIL. WPB FBC 107.2.1, 107.3.5.1.3 |
| | PLEASE SHOW ON P1-2.01A AND P1-3.02. WPB FBC 107.2.1, |
| | 107.3.5.1.3 |
| | |
| | 19. COMPLIED |
| | 20. NOT REQUIRED |
| | |
| | 21. PARTIALLY COMPLIED: PROVIDE A PLUMBING FIXTURE |
| | SCHEDULE AND SPECIFICATION, TAG IN ACCORDANCE WITH |
| | FIXTURE TAGS NOTED ON PLUMBING PLAN VIEW DRAWINGS. |
| | SECOND REQUEST: *** LAVATORIES (INCLUDE THERMOSTATIC |
| | MIXING VALVES; FPC PL 419.5) TO BE CLEAR, PLEASE ADD A |
| | THERMOSTATIC MIXING VALVE COMPLYING WITH ASSE 1070 TO |
| | P1-4.02/PLBG FIXTURE SCHEDULE |
| | SECOND REQUEST: ***SHOWERS (INCLUDE THERMOSTATIC MIXING |
| | CONTROL VALVES; FPC PL 412.3) TO BE CLEAR, PLEASE ADD |
| | P-4H SHOWER AND CONTROL VALVE TO P1-4.02/PLBG FIXTURE |
| | SCHEDULE |
| | |
| | 22. PARTIALLY COMPLIED: PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PROVIDE A WATER HEATER SCHEDULE AND DETAIL |
| | SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, |
| | HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE |
| | FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE |
| | (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) |
| | AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) |
| | PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.1.1, 607.3, |
| | 613.1, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| | 504.7, 504.7.1 AND 504.7.2. |
| | NEW COMMENT: P1-4.02/WATER HEATER DETAIL; PROVIDE A |
| | THERMAL EXPANSION CONTROL DEVICE BETWEEN THE CHECK |
| | VALVE AND THE TANK TYPE STORAGE WATER HEATER. FBC PL |
| | 607.3 |
| | NEW COMMENT: THERMAL MIXING VALVE SHALL COMPLY WITH |
| | ASSE 1017. PLEASE NOTE ON DETAIL AND WATER HEATER |
| | SCHEDULE |
| | |
| | 23. COMPLIED |
| | 24. COMPLIED |
| | |
| | 25. SECOND REQUEST: PER FBC EC C404.5.1, TABLE |
| | C404.5.1, 1/2 INCH HOT WATER TO PUBLIC LAVATORY SHALL |
| | NOT EXCEED 2 FEET FROM SOURCE. |
| | PLEASE NOTE PER FBC PL 607.2, THE DEVELOPED LENGTH OF |
| | HOT OR TEMPERED WATER IN GENERAL SHALL NOT EXCEED 50 |
| | FEET FROM THE SOURCE. RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | IF A RECIRCULATING HOT WATER SYSTEM IS PROVIDED, |
| | PROVIDE A RECIRC PUMP SCHEDULE/SPECIFICATION & DETAIL |
| | TO BE CLEAR, A RECIRCULATING OR HEAT TRACED HOT WATER |
| | SYSTEM IS REQUIRED TO KEEP 1/2 INCH HOT WATER TO PUBLIC |
| | LAVATORIES WITHIN 2 FEET OF THE SOURCE. PLEASE PROVIDE |
| | AN ACCEPTABLE PIPING METHOD TO ACCOMPLISH THIS. PROVIDE |
| | INSULATION FOR SYSTEM (SEE ITEM 26) AND IF |
| | RECIRCULATING, ADJUST WATER HEATER DETAIL AND PIPING |
| | PLAN TO REFLECT. INCLUDE RECIRC PUMP SCHEDULE IF |
| | APPLICABLE. |
| | |
| | 26. SEE ITEM 25 CLARIFICATION: PER WPB FBC 107.2.1, |
| | PROVIDE INSULATION SPECIFICATION SPEC FOR HOT WATER |
| | INSULATION COMPLY WITH FBC EC C404.4 (A-E) AND TABLE |
| | C403.2.10. |
| | THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN |
| | IN TABLE C403.2.10: |
| | ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY |
| | AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER |
| | HEATER. |
| | ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A |
| | CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM. |
| | ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO |
| | RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING. |
| | ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A |
| | HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM. |
| | ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT |
| | TRACE OR IMPEDANCE HEATING). |
| | |
| | 28. NEW COMMENT: P1-4.02/TRASH CHUTE DETAIL; SANITATION |
| | UNIT SHALL CONNECT DOWNSTREAM OF THE BACKFLOW |
| | PREVENTER. FBC PL 608.1 |
| | |
| | 29. NEW COMMENT: PLEASE SHOW LOCATION OF TRASH CHUTE |
| | AND INCLUDE PIPING IN PIPING PLANS. WPB FBC 107.2.1, |
| | 107.3.5.1.3 |
| | |
| | 30. NEW COMMENT: PLEASE PROVIDE SIZING FOR CD |
| | (CONDENSATE DRAINS). FBC PL 314.2.2. |
| | |
| | 31. NEW COMMENT: PLEASE PROVIDE CONDENSATE DRAINS FOR |
| | FCUS NOTRD ON P1-201B, P1-201C. FBC PL 314.2 |
| | |
| | 32. NEW COMMENT: P1-201B, P1-302; PLEASE PROVIDE |
| | BUILDING DRAIN FOR SANITARY FROM SECOND FLOOR BATHROOMS |
| | TO SEWER POINT OF CONNECTION. FBC PL 701.2 |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER |
| | ADDRESSING EACH ITEM. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |