| 2023-01-09 07:46:17 | 2ND REVIEW FMC |
| | PERMIT: 22101241 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON A |
| | LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN |
| | TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| | CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| | ENGINEERING ANALYSIS. FMC 403.3.1.1 |
| | |
| | 2) PROVIDE THE ZONE AIR DISTRIBUTION EFFECTIVENESS FOR |
| | EACH ZONE. FMC 403.3.1.1.1.2 |
| | |
| | 3) PROVIDE THE SYSTEM VENTILATION EFFICIENCY FOR EACH |
| | SYSTEM PROVIDING OUTDOOR AIR TO MULTIPLE ZONES. FMC |
| | 403.3.1.1.2.3.2 |
| | |
| | 4) COMMENT 7 FROM PREVIOUS REVIEW: MY COMMENT WAS MEANT |
| | FOR YOU TO EXPLAIN HOW THE DESIGN WAS REFLECTING THE |
| | REQUIRED CFM???S OF EXHAUST PER EACH WATER CLOSET AND |
| | URINAL BASED ON TABLE 403.3.1.1 AND FOOTNOTE E. I DID |
| | NOT MEAN FOR YOU TO SHOW AN EXHAUST FAN OVER EACH WATER |
| | CLOSET AND URINAL. PLEASE SHOW HOW THE MINIMUM CFM???S |
| | OF EXHAUST FOR EACH WATER CLOSET AND URINAL IS MET IN |
| | YOUR DESIGN. THERE IS NO M1-302C IN THIS SUBMITTAL. |
| | |
| | 5) SHEET M1-202B: THE PARKING GARAGE CALCULATIONS |
| | LISTED INDICATE THAT THE 1ST FLOOR PARKING GARAGE IS AN |
| | OPEN PARKING GARAGE. SHEET M1-201A SHOES A VEF-1-1. |
| | SHEET M1-302 INDICATES THIS EXHAUST FANS IS EXHAUSTING |
| | 30,000 CFM???S OF AIR FROM THE GARAGE. PLEASE EXPLAIN |
| | WHY THIS IS NEEDED IF THIS IS AN OPEN GARAGE. FBC |
| | 107.3.5 |
| | |
| | 6) COMMENT 11 FROM PREVIOUS REVIEW: THE REQUIRED FIRE |
| | DAMPERS IN THE WALL BETWEEN THE FCC ROOM AND THE MOTOR |
| | LOBBY WAS NOT ADDED TO SHEET M1-201C. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |