| 2022-11-30 16:56:41 | THRESHOLD BUILDING |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING |
| | PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY |
| | BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET |
| | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE |
| | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| | YOU CAN E MAIL ME AND ASK FOR A COPY. |
| | |
| | 1) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | 2) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. SEE "GUIDELINES |
| | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL |
| | INSPECTORS AND RESIDENT INSPECTORS". |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |