Plan Review Notes
Plan Review Notes For Permit 22101241
Permit Number 22101241
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-07 16:54:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22101241 150 CLEARWATER DR
  
 1ST REVIEW
 ELECTRONIC SIGNATURE CERTIFICATE FOR PLUMBING PLANS
 NOTES ???THE SELECTED CERTIFICATE HAS ERRORS; INVALID
 POLICY CONSTRAINT???
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR INTERCEPTOR(S) AND/OR BACKFLOW
 PREVENTER(S) AS APPLICABLE IS REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOMS INDICATING THE FOLLOWING:
 ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1
 ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***E) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***F) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ***H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE
 ***I) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2.
 ***J) LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ***K) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***L) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 ***M) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 603.3.
 ***N) DRINKING FOUNTAINS SHOWING COMPLIANCE WITH 306.2,
 306.3, 307.2, 602.4, 602.5, 602.7
 ***O) ROLL IN TYPE SHOWER COMPARTMENT; COMPLY WITH FBC
 ACC 608.2.2, 608.2.2.1, 608.3, 608.3.2, 608.4, 608.5,
 309.4, 608.5.2, 608.7.
  
 2. PER WPB FBC 107.2.1, REGARDING PLAN SHEET A1-402, TO
 SHOW COMPLIANCE WITH FBC PL 403.1 AND TABLE 403.1,
 PROVIDE OCCUPANCY AND OCCUPANCY LOAD FOR THE BATHROOMS
 SERVICING THE NORTH GARAGE GROUND FLOOR.
  
 3. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE WALL
 FINISHES FOR WALLS ADJACENT TO WATER CLOSETS AND
 SERVICE SINKS. COMPLY WITH FBC PL 310.3, FBC 1210.2.2
  
 4. PLAN PAGES 262 P1-201A NORTH GARAGE GROUND FLOOR
 PLAN PLUMBING AND 114 C-15 WSU PLAN: SANITARY BUILDING
 DRAINS/BUILDING SEWERS DO NOT MATCH UP TO CIVIL
 CONNECTIONS. PER WPB FBC 107.2.1 AND 107.3.5.1.3,
 PLEASE CLARIFY AND RECONCILE.
  
 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE
 MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE
 RISER DIAGRAMS
  
 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING
 PLAN VIEW FOR SOUTH PLAZA SECOND FLOOR PLUMBING.
 INCLUDE WATER HEATER.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING
 AND DRAIN FOR SOUTH GARAGE LEVEL 2 AREA DRAIN
  
 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CALCULATIONS
 FOR STORM PIPING SHALL BE ACCUMULATED AND APPLIED TO
 SIZING OF ALL STORM PIPING TO INCLUDE VERTICAL
 CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, BUILDING
 STORM SEWERS AND ANY HORIZONTAL BRANCHES OF SUCH DRAINS
 OR SEWERS PER FBC PL 1106.1.
 CALCULATIONS FOR AREA SHALL INCLUDE VERTICAL SURFACES
 AS WELL AS HORIZONTAL SURFACES. FBC PL 1106.4
  
 9. PROVIDE SECONDARY ROOF DRAINS OR SCUPPERS IN
 ACCORDANCE WITH FBC PL SECTION 1108.
  
 10. PER WPB FBC 107.3.5.1.3, FBC PL 604.1, 604.3,
 PROVIDE CALCULATIONS FOR SIZING OF WATER DISTRIBUTION.
  
 11. PER WPB FBC 107.3.5.1.3, FBC PL 710.1, PROVIDE
 CALCULATIONS FOR SIZING OF SANITARY DRAINAGE.
  
 12. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SIZING
 OF SANITARY DRAINAGE, SANITARY VENTS, SANITARY FORCE
 MAINS, WATER DISTRIBUTION, STORM DRAINAGE, GD DRAINAGE
 ON PLAN VIEWS AND RISER DIAGRAMS
  
 13. PER WPB FBC 107.2.1 AND 107.3.5.1.3, IDENTIFY
 SANITARY DRAIN LINES ON PLAN VIEWS
  
 14. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PLEASE PROVIDE
 A PLUMBING LEGEND; I.E., GD=?, FM=?, ETC.
  
 15. REFERENCE TO DETAILS ARE NOTED ON THE PLUMBING
 PLANS. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 DETAIL(S) FOR THE FOLLOWING:
 ***A) SUMP PITS AND PUMP WITH PUMP
 SCHEDULE/SPECIFICATION
 ***B) HOSE BIBB PROTECTION IN PARKING AREAS
  
 16. PER FBC PL 901.2.1, PROVIDE VENT FOR THE SANITARY
 HUB DRAIN(S)
  
 17. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE DETAIL
 FOR TYPICAL SANITARY HUB DRAIN AND INDIRECT WASTE
 CONNECTION
  
 18. P1-2.01A: SANITARY BRANCH FROM BATHROOMS ADJACENT
 TO BICYCLE PARKING SPACE IS SHOWN DISCHARGING INTO THE
 FM (FORCE MAIN?) FROM ELEVATOR SUMP PUMP AT GRID LINES
 G-13 AND THEN INTO HD (HUB DRAIN?) IS THIS BRANCH A
 SUBDRAIN UNABLE TO DRAIN BY GRAVITY INTO BUILDING
 DRAIN? IF SO, IT SHALL BE DISCHARGED INTO THE SANITARY
 BUILDING DRAIN IN ACCORDANCE WITH FBC PL 712.3.5,
 THROUGH A SEWAGE PUMP OR SEWAGE EJECTOR PER FBC PL
 712.4. AN EQUIPMENT SCHEDULE/SPECIFICATION FOR PUMP AND
 SUMP WITH A DETAIL SHALL BE PROVIDED. IF NOT A SUBDRAIN
 THEN CONNECT DIRECTLY TO THE BUILDING DRAIN PER FBC PL
 712.1, NOT TO THE FM (FORCE MAIN?).
  
 19. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE PIPING
 MATERIAL SPEC FOR EACH SYSTEM (SANITARY DRAINAGE,
 SANITARY FORCE MAINS, VENT PIPING, STORM DRAINAGE,
 WATER DISTRIBUTION, A/C CONDENSATE) TO INCLUDE PIPE,
 VALVES, FITTINGS AND JOINTS. COMPLY WITH FBC PL
 CHAPTERS 3, 6, 7, 9 AND 11.
  
 20. PROVIDE MINIMUM AVAILABLE WATER PRESSURE AT THE
 HIGHEST POINT OF THE WATER DISTRIBUTION SYSTEM. FBC PL
 604.3 AND TABLE 604.3
  
 21. PROVIDE A PLUMBING FIXTURE SCHEDULE AND
 SPECIFICATION, TAG IN ACCORDANCE WITH FIXTURE TAGS
 NOTED ON PLUMBING PLAN VIEW DRAWINGS. ITEMS SHALL
 INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
 ***WATER CLOSETS
 *** LAVATORIES (INCLUDE THERMOSTATIC MIXING VALVES; FPC
 PL 419.5)
 ***SINKS
 ***URINALS
 ***SHOWERS (INCLUDE THERMOSTATIC MIXING CONTROL VALVES;
 FPC PL 412.3)
 ***DRINKING FOUNTAINS
 ***HOSE BIBS
 ***WALL HYDRANTS
 ***TRAP PRIMER DEVICES
 ***ACCESS PANELS
 ITEMS SHALL INCLUDE APPLICABLE FAUCETS, CONTROL VALVES,
 ETC.
  
 22. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 WATER HEATER SCHEDULE AND DETAIL SHOWING HEATER
 W/STORAGE CAPACITY, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , THERMAL EXPANSION CONTROL DEVICE (INCLUDING
 SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER
 HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER WPB
 FPC 107.2.1; COMPLY WITH FBC PL 607.1.1, 607.3, 613.1,
 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7,
 504.7.1 AND 504.7.2.
 PROVIDE ENERGY EFFICIENCY SHOWING COMPLIANCE WITH FBC
 EC TABLE C404.2.
  
 23. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 PLUMBING DRAIN SCHEDULE/SPECIFICATION
 ***FLOOR DRAINS
 ***GD
  
 24. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SUMP
 PUMP SCHEDULE/SPECIFICATION
  
 25. PER FBC EC C404.5.1, TABLE C404.5.1, 1/2 INCH HOT
 WATER TO PUBLIC LAVATORY SHALL NOT EXCEED 2 FEET FROM
 SOURCE.
 PLEASE NOTE PER FBC PL 607.2, THE DEVELOPED LENGTH OF
 HOT OR TEMPERED WATER IN GENERAL SHALL NOT EXCEED 50
 FEET FROM THE SOURCE. RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
 IF A RECIRCULATING HOT WATER SYSTEM IS PROVIDED,
 PROVIDE A RECIRC PUMP SCHEDULE/SPECIFICATION & DETAIL
  
 26. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION SPEC FOR HOT WATER INSULATION COMPLY WITH
 FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:
 ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY
 AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER
 HEATER.
 ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A
 CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM.
 ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO
 RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING.
 ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A
 HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM.
 ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT
 TRACE OR IMPEDANCE HEATING).
  
 27. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER AND
 SUPPORT DETAILS SHOWING COMPLIANCE WITH FBC PL TABLE
 308.5.
  
 28. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 CROSS-SECTION SHOWER WALL/FLOOR/DRAIN AND THRESHOLD
 DETAIL TO SHOW COMPLIANCE WITH FBC PL 421.5.2, 421.4.1,
 421.5
  
 29. PER FBC FL 1002.4.1, PROVIDE TRAP SEAL PROTECTION
 FOR THE FLOOR DRAIN. PER WPB FBC 107.2.1, PROVIDE A
 TRAP SEAL PROTECTION SPECIFICATION AND DETAIL COMPLYING
 WITH ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2,
 1002.4.1.3 OR 1002.4.1.4.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A COMPREHENSIVE RESPONSE LETTER
 ADDRESSING EACH ITEM.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  