2022-11-29 06:23:101ST REVIEW FMC
 PERMIT: 22101241
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 3) WHERE ARE THE CALCULATIONS FOR THE PARKING GARAGE
 VENTILATION? IF THE PARKING GARAGE IS ENCLOSED PLEASE
 SHOW THAT THE CONDENSING UNITS MOUNTED IN THE ENCLOSED
 PARKING GARAGE WILL BE SUPPLIED THE REQUIRED AIR
 CIRCULATION FOR EACH CONDENSING UNIT. MANUFACTURES
 INSTRUCTIONS.
  
 4) REVISE THE MECHANICAL DRAWINGS TO ADD A NOTE THAT
 THE GENERATOR WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DOCUMENT SUBMITTAL AND PLAN REVIEW.
  
 5) PROVIDE A CO,NO2 LAYOUT, COVERAGE AREA FOR EACH
 SENSOR, SHEET FOR THE GARAGES. FBC 107.3.5
  
 PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH OCCUPANCY
 CLASSIFICATION FOR THIS PROJECT. FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
 6) SHEET M1-201A: REVISE THE BATH EXHAUST FANS TO
 REFLECT EACH WATER CLOSET OR URINAL. ADD A NOTE ON THE
 DRAWINGS TO INDICATE HOW THE EXHAUST FANS FOR THE BATH
 ROOMS WILL BE CONTROLLED. FMC TABLE 403.3.1.1 FOOTNOTE
 E
  
 7) SHEET M1-201A: MISSING A FD FOR THE INTAKE DUCT 14 X
 6 AT THE WALL PENETRATION OF THE MECHANICAL ROOM. FMC
 607
  
 8) SHEET M1-201A: MISSING A FD FOR THE 18 X 12 SUPPLY
 DUCT LEAVING THE MECHANICAL ROOM TO SERVE THE LOBBY.
 FMC 607
  
 9) SHEET M1-201A: PROVIDE THE VENTILATION CALCULATIONS
 FOR THE BIKE STORAGE ROOM. FMC TABLE 403.3.1.1
  
 10) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE
 REQUIRED FD???S IN THE SUPPLY AND RETURN DUCT
 PENETRATING THE RATED WALL SEPARATING THE MOTOR LOBBY
 FROM THE FCC ROOM. FMC 607
  
 11) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE
 OUTDOOR AIR DUCT SIZE FOR FCU-1-4 IN THE FCC ROOM. FBC
 107.3.5
  
 12) SHEET M1-202C: PROVIDE THE CFM???S OF SUPPLY AIR TO
 THE BATHROOMS FROM FCU-2.10. FBC 107.3.5
  
 13) SHEET M1-202C: SHOW THE MEN???S BATH EXHAUST MEETS
 THE REQUIRES OF TABLE 403.3.1.1
  
 14) SHEET LS-211 INDICATES A TERRACE ON THE ROOF FOR A
 FUTURE TENANT, SHEET M1-204C INDICATES THIS SAME AREA
 TO BE THE LOCATION OF CONDENSING UNIT RACK FOR FUTURE
 SPACE AC SYSTEMS. PLEASE BE CONSISTENT WITH BOTH
 SHEETS. FBC 107.3.5
  
 15) SHEET M1-301: REVISE THE GENERAL NOTES TO REFLECT
 THE CURRENT 2020 7TH EDITION FLORIDA BUILDING CODES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  