| 2022-11-29 06:23:10 | 1ST REVIEW FMC |
| | PERMIT: 22101241 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 3) WHERE ARE THE CALCULATIONS FOR THE PARKING GARAGE |
| | VENTILATION? IF THE PARKING GARAGE IS ENCLOSED PLEASE |
| | SHOW THAT THE CONDENSING UNITS MOUNTED IN THE ENCLOSED |
| | PARKING GARAGE WILL BE SUPPLIED THE REQUIRED AIR |
| | CIRCULATION FOR EACH CONDENSING UNIT. MANUFACTURES |
| | INSTRUCTIONS. |
| | |
| | 4) REVISE THE MECHANICAL DRAWINGS TO ADD A NOTE THAT |
| | THE GENERATOR WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION, DOCUMENT SUBMITTAL AND PLAN REVIEW. |
| | |
| | 5) PROVIDE A CO,NO2 LAYOUT, COVERAGE AREA FOR EACH |
| | SENSOR, SHEET FOR THE GARAGES. FBC 107.3.5 |
| | |
| | PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH OCCUPANCY |
| | CLASSIFICATION FOR THIS PROJECT. FMC 403.3.1.1 AND |
| | TABLE 403.3.1.1 |
| | |
| | 6) SHEET M1-201A: REVISE THE BATH EXHAUST FANS TO |
| | REFLECT EACH WATER CLOSET OR URINAL. ADD A NOTE ON THE |
| | DRAWINGS TO INDICATE HOW THE EXHAUST FANS FOR THE BATH |
| | ROOMS WILL BE CONTROLLED. FMC TABLE 403.3.1.1 FOOTNOTE |
| | E |
| | |
| | 7) SHEET M1-201A: MISSING A FD FOR THE INTAKE DUCT 14 X |
| | 6 AT THE WALL PENETRATION OF THE MECHANICAL ROOM. FMC |
| | 607 |
| | |
| | 8) SHEET M1-201A: MISSING A FD FOR THE 18 X 12 SUPPLY |
| | DUCT LEAVING THE MECHANICAL ROOM TO SERVE THE LOBBY. |
| | FMC 607 |
| | |
| | 9) SHEET M1-201A: PROVIDE THE VENTILATION CALCULATIONS |
| | FOR THE BIKE STORAGE ROOM. FMC TABLE 403.3.1.1 |
| | |
| | 10) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE |
| | REQUIRED FD???S IN THE SUPPLY AND RETURN DUCT |
| | PENETRATING THE RATED WALL SEPARATING THE MOTOR LOBBY |
| | FROM THE FCC ROOM. FMC 607 |
| | |
| | 11) SHEET M1-201C: REVISE THE DRAWING TO INCLUDE THE |
| | OUTDOOR AIR DUCT SIZE FOR FCU-1-4 IN THE FCC ROOM. FBC |
| | 107.3.5 |
| | |
| | 12) SHEET M1-202C: PROVIDE THE CFM???S OF SUPPLY AIR TO |
| | THE BATHROOMS FROM FCU-2.10. FBC 107.3.5 |
| | |
| | 13) SHEET M1-202C: SHOW THE MEN???S BATH EXHAUST MEETS |
| | THE REQUIRES OF TABLE 403.3.1.1 |
| | |
| | 14) SHEET LS-211 INDICATES A TERRACE ON THE ROOF FOR A |
| | FUTURE TENANT, SHEET M1-204C INDICATES THIS SAME AREA |
| | TO BE THE LOCATION OF CONDENSING UNIT RACK FOR FUTURE |
| | SPACE AC SYSTEMS. PLEASE BE CONSISTENT WITH BOTH |
| | SHEETS. FBC 107.3.5 |
| | |
| | 15) SHEET M1-301: REVISE THE GENERAL NOTES TO REFLECT |
| | THE CURRENT 2020 7TH EDITION FLORIDA BUILDING CODES. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |