| Plan Review Notes For Permit 22101241 |
| Permit Number |
22101241 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-02 12:20:02 | FIRE REVIEW COMMENTS: | | | | | | (1) FIRE DEPARTMENT CONNECTIONS SHALL NOT BE LOCATED | | | MORE THAN 100 FEET FROM THE NEAREST FIRE HYDRANT | | | CONNECTED TO AN APPROVED WATER SUPPLY PER THE | | | REQUIREMENTS OF NFPA 14. | | | | | | (2) PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, AND | | | NFPA 101 FOR THE APPLICABLE OCCUPANCY CHAPTER TO | | | INCLUDE CHAPTER 42 (STORAGE OCCUPANCIES). | | | | | | (3) NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA 14 | | | COMPLIANT STANDPIPE SYSTEM SHALL HAVE SEPARATE SHOP | | | DRAWINGS TO BE SUBMITTED AND APPROVED PRIOR TO | | | INSTALLATION. TEMPORARY STANDPIPES ARE REQUIRED WHEN | | | THE BUILDING REACHES THREE LEVELS OR 35??? IN HEIGHT | | | WHILE BEING CONSTRUCTED. | | | | | | (4) SEVERAL REFERENCES TO CITY OF MIAMI, OR | | | HEATHER/OCEAN ADDRESSING. CORRECT FOR JURISDICTION OF | | | CITY OF WEST PALM BEACH, AND CORRECT STREET ADDRESSING. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|