2022-11-02 12:20:02FIRE REVIEW COMMENTS:
  
 (1) FIRE DEPARTMENT CONNECTIONS SHALL NOT BE LOCATED
 MORE THAN 100 FEET FROM THE NEAREST FIRE HYDRANT
 CONNECTED TO AN APPROVED WATER SUPPLY PER THE
 REQUIREMENTS OF NFPA 14.
  
 (2) PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, AND
 NFPA 101 FOR THE APPLICABLE OCCUPANCY CHAPTER TO
 INCLUDE CHAPTER 42 (STORAGE OCCUPANCIES).
  
 (3) NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA 14
 COMPLIANT STANDPIPE SYSTEM SHALL HAVE SEPARATE SHOP
 DRAWINGS TO BE SUBMITTED AND APPROVED PRIOR TO
 INSTALLATION. TEMPORARY STANDPIPES ARE REQUIRED WHEN
 THE BUILDING REACHES THREE LEVELS OR 35??? IN HEIGHT
 WHILE BEING CONSTRUCTED.
  
 (4) SEVERAL REFERENCES TO CITY OF MIAMI, OR
 HEATHER/OCEAN ADDRESSING. CORRECT FOR JURISDICTION OF
 CITY OF WEST PALM BEACH, AND CORRECT STREET ADDRESSING.
  