Plan Review Notes
Plan Review Notes For Permit 22101241
Permit Number 22101241
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-01 14:39:19FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO LOAD CALCULATIONS SHOWN 215.5
  
 220.1 SCOPE.
  
 THIS ARTICLE PROVIDES REQUIREMENTS FOR CALCULATING
 BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. PART I
 PROVIDES GENERAL REQUIREMENTS FOR CALCULATION METHODS.
 PART II PROVIDES CALCULATION METHODS FOR BRANCH-CIRCUIT
 LOADS. PARTS III AND IV PROVIDE CALCULATION METHODS FOR
 FEEDER AND SERVICE LOADS. PART V PROVIDES CALCULATION
 METHODS FOR FARM LOADS.
  
 220.40 GENERAL.
  
 THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE
 LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS
 SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE,
 AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART
 III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED.
  
  
 2) NO RISER DIIAGRAM SHOWN 215.5
  
 215.5 DIAGRAMS OF FEEDERS.
  
 IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A
 DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR
 TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM
 SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING
 DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO
 BE USED.
  
  
 3) NO FAULT CURRENT CALCULATION SHOWN 110.9
  
 110.9 INTERRUPTING RATING.
  
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE AN INTERRUPTING RATING AT NOMINAL CIRCUIT
 VOLTAGE AT LEAST EQUAL TO THE CURRENT THAT IS AVAILABLE
 AT THE LINE TERMINALS OF THE EQUIPMENT.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT OTHER THAN
 FAULT LEVELS SHALL HAVE AN INTERRUPTING RATING AT
 NOMINAL CIRCUIT VOLTAGE AT LEAST EQUAL TO THE CURRENT
 THAT MUST BE INTERRUPTED.
  
  
 4) PANELS G2A,B THROUGH GA,B LOADS FIGURE AT 100% WHEN
 THEY SHALL BE AT 125% 625.41
  
 625.41 OVERCURRENT PROTECTION.
  
 OVERCURRENT PROTECTION FOR FEEDERS AND BRANCH CIRCUITS
 SUPPLYING EQUIPMENT SHALL BE SIZED FOR CONTINUOUS DUTY
 AND SHALL HAVE A RATING OF NOT LESS THAN 125 PERCENT OF
 THE MAXIMUM LOAD OF THE EQUIPMENT. WHERE NONCONTINUOUS
 LOADS ARE SUPPLIED FROM THE SAME FEEDER, THE
 OVERCURRENT DEVICE SHALL HAVE A RATING OF NOT LESS THAN
 THE SUM OF THE NONCONTINUOUS LOADS PLUS 125 PERCENT OF
 THE CONTINUOUS LOADS.
  
 625.42 RATING.
  
 THE EQUIPMENT SHALL HAVE SUFFICIENT RATING TO SUPPLY
 THE LOAD SERVED. ELECTRIC VEHICLE CHARGING LOADS SHALL
 BE CONSIDERED TO BE CONTINUOUS LOADS FOR THE PURPOSES
 OF THIS ARTICLE. WHERE AN AUTOMATIC LOAD MANAGEMENT
 SYSTEM IS USED, THE MAXIMUM EQUIPMENT LOAD ON A SERVICE
 AND FEEDER SHALL BE THE MAXIMUM LOAD PERMITTED BY THE
 AUTOMATIC LOAD MANAGEMENT SYSTEM.
  
  
 5) SITE LIGHTING, GENERATOR, FIRE ALARM, AND ALL LOW
 VOLTAGE SYSTEMS REQUIRE SEPARATE PERMITS AND PLANS.